Liebert APM UPS Modular & Scalable Digital UPS with integrated Power Distribution Unit User & Installation Manual Version Revision date BOM V1.0 January 04, 2010 31012118 Emerson Network Power provides customers with technical support. Users may contact the nearest Emerson local sales office or service center. Copyright © 2009 by Emerson Network Power Co., Ltd. All rights reserved. The contents in this document are subject to change without notice. Emerson Network Power Co., Ltd. Address: No.1 Kefa Rd.
Safety Precautions This manual contains information concerning the installation and operation of this Liebert APM modular UPS This manual must be read prior to installation. The UPS must be commissioned and serviced by engineers approved by the manufacturer (or its agent). Failure to do so could result in personnel safety risk, equipment malfunction and invalidation of warranty. The UPS has been designed for commercial or industrial use only, and is not for use in any life support application.
Battery voltage exceeds 400Vdc All physical battery maintenance and servicing requires the use of a tool or a key and should be carried out only by trained personnel. Special care should be taken when working with the batteries. When connected together, the battery terminal voltage will exceed 400Vdc and is potentially lethal. Battery manufacturers supply details of the necessary precautions to be observed when working on, or in the vicinity of, a large bank of battery cells.
Contents Chapter 1 Installation .......................................................................................................................................................... 1 1.1 Introduction ........................................................................................................................................................... 1 1.2 Preliminary Checks .............................................................................................................................
2.2.2 Battery Mode ........................................................................................................................................... 17 2.2.3 Automatic Restart Mode .......................................................................................................................... 17 2.2.4 Bypass Mode........................................................................................................................................... 17 2.2.5 Maintenance Bypass Mode .....
Chapter 5 Service ............................................................................................................................................................. 35 5.1 Service Procedures Of Power Module, Bypass Module And Output Distribution Module ................................... 35 5.1.1 Notes ....................................................................................................................................................... 35 5.1.2 Power Module Service Procedures ....
Chapter 1 Installation 1 Chapter 1 Installation This chapter introduces the installation of Liebert APM modular UPS, including preliminary checks, location, positioning, cable connection and installation drawings. 1.1 Introduction This chapter describes the requirements that must be taken into account when planning the positioning and cabling of the UPS. This chapter is a guide to general procedures and practices that should be observed by the installing engineer.
2 Chapter 1 Installation If necessary, install a system of room extractor fans to avoid room temperature build-up. Optional air filters are available if the UPS is to operate in a dusty environment. Note: The UPS is suitable for mounting on concrete or other non-combustible surface only. 1.3.2 Battery Room The batteries will generate small amount of hydrogen and oxygen at the end of battery charge.
Chapter 1 Installation 3 1.4.1 UPS Composition The UPS structure is shown in Figure 1-1. The UPS configuration is provided in Table 1-1.
4 Chapter 1 Installation 1.4.3 Clearances The UPS has no ventilation grilles at either side; therefore, no clearance is required at either side. To enable routine tightening of power terminations within the UPS, in addition to meeting any local regulations, it is recommended to provide adequate clearance in the front and at the back of the cabinet for unimpeded passage of personnel with the doors fully opened for accessing cable termination. Refer to Figure 1-15 for the positioning of the cabinet.
Chapter 1 Installation 5 DIP switch Fixing holes Ready switch A amplified view Power module A Figure 1-2 Installing power module Installation procedures of Optional output distribution modules Use the following procedures of install the output distribution module: 1. Insert the module in the installation position, and push it into the cabinet. 2. Secure the module to the cabinet through the fixing holes on both sides of the front panel of the module. 1.4.
6 Chapter 1 Installation Earth Leakage Any residual current detector (RCD) installed upstream of the UPS input supply must: z be sensitive to DC unidirectional pulses (Class A) in power distribution network z be insensitive to transient current pulses z have an average sensitivity, adjustable between 0.
Chapter 1 Installation 7 1. Protective earth cable: Follow the most direct route possible to connect the earth cable to the cabinet. The earth cable shall be sized in accordance with the AC supply fault rating, cable lengths and type of protection. Typical 2 cross sectional area (CSA) is 80mm (150kVA) according to AS / IEC60950-1. 2. When sizing battery cables, a maximum volt drop of 4Vdc is permissible at the current ratings given in Table 1-3.
8 Chapter 1 Installation at the rear of the UPS cabinet. Tighten the output neutral bar connections to 5Nm (M6 bolt). Ensure correct phase rotation. z In case output distribution modules are not installed, please connect the output cables between the output terminals in the front of the UPS cabinet and the loads, and connect the output earth cable to the output earth terminal at the rear of the UPS cabinet.
Chapter 1 Installation Figure 1-5 Battery Cabinet Details Figure 1-6 Battery Connection 1.7 Control And Communications As shown in Figure 1-7, the bypass module provides dry contact ports (J5 ~ J10) and communication ports (RS232 port and SNMP card ports) on the front panel.
10 Chapter 1 Installation J8 J5 J9 J6 J10 J7 Figure 1-7 RS232 port SNMP card ports Dry contact ports and communication ports The UPS accepts external signalling from voltage-free (dry) contacts connected to push-in input dry contact terminal. Subject to prior software programming, the signalling is accepted by the UPS when relevant terminals and the +12V terminals are shorted. All control cables must be routed separately from the power cables, and must be double 2 2 insulated. A typical 0.5mm to 1.
Chapter 1 Installation 11 1.7.2 BCB Port J6 is the battery circuit breaker (BCB) port. The port is shown in Figure 1-6 and described in Table 1-9. 12V 12V 12V Figure 1-9 Table 1-6 Position Name J6.1 DRV J6.2 FB J6.3 GND J6.
12 Chapter 1 Installation 1.7.4 Output Dry Contact Port J5 is the output dry contact port, providing two relay output dry contact signals. The port is shown in Figure 1-12 and described in Table 1-8. Figure 1-12 Table 1-8 Position BFP_O BFP_S BFP_C J5 Output dry contact port Description of output dry contact port Name Description BFP_O Bypass feedback protection relay (normally silicon-controlled rectifier (SCR) is shorted J5.3 BFP_S Bypass feedback protection relay common J5.
Chapter 1 Installation 13 1.7.6 Other Communication Interface The RS232 port provides serial data and is intended for use by authorized commissioning and service personnel in UPS commissioning and service. Liebert APM UPS has facility of internally fitted SNMP and Modbus card options. 1.
Installation 1100 1126 1137 Chapter 1 1677 14 2000 971 Top view 600 Front view Figure 1-15 UPS installation size (unit: mm) SPM monitoring module Output terminals Output terminals Output earth bars (2 pcs respectively on both sides) Output neutral bars (2 pcs respectively on both sides) Input earth terminal Battery terminals + N - U Input terminals V W N A Output earth terminal A amplified view Figure 1-16 Rear view of UPS (door open) with output distribution modules Liebert APM Mod
Chapter 1 Output terminals A N C B A A amplified view Figure 1-17 Front view of UPS (door open) without output distribution modules Liebert APM Modular UPS User & Installation Manual Installation 15
16 Chapter 2 Operation Chapter 2 Operation This chapter introduces the basic knowledge of UPS operation, including the operating theory, operation mode, battery management and battery protection of the UPS. Warning: hazardous mains and battery voltage present behind covers 1. No user-serviceable parts are located behind covers that require a tool for their removal. 2. Only qualified service personnel are authorised to remove such covers. 2.
Chapter 2 Operation 17 During normal operating conditions, the inverter output and bypass supply must be fully synchronized so as to achieve a clean (no-break) load transfer between the inverter output and static bypass line. The synchronization between the inverter output and static bypass is achieved through the inverter control electronics, which make the inverter frequency track that of the static bypass supply, provided that the bypass remains within an acceptable frequency window.
18 Chapter 2 Operation interruption is programmable but typically set to be less than 3/4 of an electrical cycle, for example, less than 15ms (50Hz) or less than 12.5ms (60Hz). 2.2.5 Maintenance Bypass Mode If UPS maintenance or repaired is needed, you may use the manual maintenance bypass switch to transfer to the load to the maintenance bypass, with no interruption in power to the load.
Chapter 2 Operation 19 2.3.2 Advanced Function——Battery Self-Test And Self-Service At periodic intervals 20% of the rated capacity of the battery will be discharged automatically. The minimum amount of load must exceed 20% of the nominal rating of the UPS. If the load is less than 20%, auto-discharge cannot be executed. The periodic interval can be set from 30 days to 360 days. The periodic testing can also be inhibited.
20 Chapter 3 Operating Procedures Chapter 3 Operating Procedures This chapter provides detailed operating procedures of the UPS. All control keys and LED indication mentioned in these procedures are identified in Chapter 4 Operator Control And Display Panel. Audible alarm may sound at various points during these procedures. It can be canceled at any time by pressing the SILENCE ON/OFF key. Warning: hazardous mains and battery voltage present behind covers 1.
Chapter 3 Operating Procedures 21 3.2.1 Start-Up Procedures (Into Normal Mode) Procedures are as follows for starting the UPS from a fully powered-down condition: Warning During these procedures the output terminals are live. If any load equipment is connected to the UPS output terminals, please check with the load user and ascertain whether it is safe to apply power to the load. If the load is not ready to receive power, open the corresponding output distribution switch. 1.
22 Chapter 3 Operating Procedures Battery start button Figure 3-2 Location of battery start button 3.3 Procedures Of Transfer Between Operation Modes 3.3.1 Transfer From Normal Mode To Battery Mode Open the input switch to cut off the mains input, and the UPS enters battery mode. To return to normal mode, wait a few seconds and close the input switch to connect the mains power to the UPS. The rectifiers will restart automatically after 10 seconds and resume feeding power to the inverters. 3.3.
Chapter 3 Operating Procedures 23 3. Open the input switch and output switch. Caution 1. The load is not protected from normal supply aberrations when the UPS is operating in maintenance bypass mode. 2.
24 Chapter 3 Operating Procedures 3.8 Changing The Current Date And Time To change the system date and time, carry out the following procedures: 1. From the Output menu, press the F3 or F4 (left or right) key as needed to select the Settings menu. 2. Press the F5 (enter) key to move the cursor to the data window on the screen. 3. Use the F3 or F4 (up or down) key to select the Date & time option, then press the F5 (enter) key. 4.
Chapter 4 Operator Control And Display Panel 25 Chapter 4 Operator Control And Display Panel This chapter expounds the functions and use of the components on the operator control and display panel of the UPS, and provides LCD display information, including the LCD screen types, detailed menu messages, prompt windows and UPS alarm list. 4.1 Introduction The operator control and display panel is located on the front door of the UPS.
26 Chapter 4 Operator Control And Display Panel 4.1.1 LED Indicators The LED indicators mounted on the mimic power flow chart represent the various power paths and current UPS operational status. The indicators are described in Table 4-2.
Chapter 4 Operator Control And Display Panel 27 4.1.4 LCD And Menu Keys The operator control and display panel provides an LCD and five menu keys (F1, F2, F3, F4, F5). The menu keys are described in Table 4-5.
28 Chapter 4 Operator Control And Display Panel 4.2.2 Primary Screen After the UPS starts and finishes self-test, the primary screen appears, as shown in Figure 4-3. The primary screen is divided into four windows: system information window, menu window, data window and keypad window. ADAPT PM150 相电压(V) 相电流(A) 频率(Hz) 线电压(V) 功率因数 A(AB) 220 20.5 50.1 380 0.99 System information window 12:30:36 B(BC) 220 20.5 50.1 380 0.99 C(CA) 220 20.5 50.1 380 0.
Chapter 4 Operator Control And Display Panel 29 4.2.3 Default Screen During UPS operation, if there is no alarm within two minutes, the default screen will appear, as shown in Figure 4-5. After a short delay, the LCD backlight will turn off. Pressing any keys (F1 ~ F5) restores the default screen. Liebert APM F1 F2 Figure 4-5 F3 12:30:36 F4 F5 Default screen 4.3 Detailed Description Of Menu Items The description that follows refers to the LCD primary screen shown on Figure 4-3.
30 Chapter 4 Operator Control And Display Panel Menu Load System Battery Item Power factor Sout (kVA) Sout: apparent power Pout (kW) Pout: active power Qout (kVAR) Qout: reactive power Load level (%) The percentage of the UPS rating load Crest factor Output current crest factor Sout (kVA) Sout: apparent power Pout (kW) Pout: active power Qout (kVAR) Qout: reactive power Battery voltage (V) Battery bus voltage Battery current (A) Battery bus current Battery temperature (°C) Batte
Chapter 4 Menu Command (initiate, stop battery, system test or freshening charge Version Operator Control And Display Panel Item 31 Explanation Battery maintenance test This test performs a partial discharge of the battery to obtain a rough estimate of the battery capacity. Load must be between 20% and 100% Battery capacity test This test performs a full discharge of the battery to obtain a precise measure of the battery capacity.
32 Chapter 4 Operator Control And Display Panel 4.5 Alarm List The following table provides the complete list of UPS alarm messages supported for display either on the Event menu or on the Records menu as described in Table 4-9. Table 4-9 Alarm list Alarm Explanation Inverter comm. fail Internal communication failure between monitoring board and inverters Rectifier comm. fail Internal communication failure between monitoring board and rectifiers Parallel comm.
Chapter 4 Alarm Inverter asynchronous Operator Control And Display Panel 33 Explanation This alarm is triggered by an inverter software routine when the inverter and bypass waveforms are misaligned by more than six degrees in phase. The amplitude threshold is fixed for ±10% rating. This alarm resets automatically once the condition is no longer true. 1. First check if the alarm Bypass unable to trace or Bypass abnormal occurs. If so, solve it first. 2. Verify the waveform of the bypass voltage.
34 Chapter 4 Operator Control And Display Panel Alarm Explanation Alarm silence SILENCE ON/OFF key pressed Turn on fail Inverters failed to turn on when the INVERTER ON key was pressed.
Chapter 5 Service 35 Chapter 5 Service This chapter introduces the UPS service, including the service procedures of the power module, bypass module and output distribution module, and the replacement of air filter. 5.1 Replacement Procedures Of Power Module, Bypass Module And Output Distribution Module 5.1.1 Notes 1. Only the customer service engineers shall service the power modules, bypass module and output distribution modules. 2.
36 Chapter 5 Service 6. After servicing the module, push the module (at least 10s after another) into the cabinet, and tighten the screws on both sides. 7. Close the UPS output switch and input switch in turn. Two minutes later, the bypass indicator on the operator control and display panel turns on, indicating the UPS is operating in bypass mode. 8.
Chapter 6 Specifications 37 Chapter 6 Specifications The chapter provides the UPS specifications. 6.1 Conformity And Standards The UPS has been designed to conform to the European and international standards listed in Table 6-1.
38 Chapter 6 Specifications 6.4 Electrical Characteristics (Input Rectifier) Table 6-4 Rectifier AC input (mains) Rated power (kVA) Unit 150 Rated AC input voltage1 Vac 380/400/415 (3-phase and sharing neutral with the bypass input) Input voltage tolerance2 Vac 305 ~ 477; 304 ~ 208 (output derated below 70%) Frequency2 Hz 50/60 (tolerance: 40Hz ~ 70Hz) Power factor kW/kVA, full load (half load) 0.99 (0.
Chapter 6 Specifications 6.
40 Chapter 6 Specifications 6.
Appendix 1 BCB Model Selection And Connection 41 Appendix 1 BCB Model Selection And Connection Table 1 Selection reference table of BCB rated current and connection cable cross CSA Unit 30 60 90 120 150 Max battery discharge current at full load Rated power (kVA) A 105 210 315 420 525 Reference rated current of circuit breaker A 150 250 350 450 550 35 70 105 140 175 CSA of connection cable mm 2 Note : 1.