Liebert DS Components and Nomenclature
5Liebert
®
DS
Figure 3 Liebert DS model number nomenclature
Not all combinations of options are available on all units.
Digital Scroll Compressors
Not available on 077 and 105 models
Not compatible with SCR reheat because digital scroll provides variable capacity control
EC Fans, Direct-Drive
Not available on upflow (VS) configuration
Liebert Econ-O-Coil
not available on 028, 035, 042 models with 208/230V
Steam Generating Canister Humidifier
Not available on upflow (VS) configurations
Not available on EC fan configurations
575 Volt Option Limitations
EC fans not available on 105 model
Digital scroll compressors available only on 053, 070 models
GLYCOOL Liebert Economizer Models
105 model requires semi-hermetic compressors only, so as to prevent potential coil freezing
Turning Vanes
Not available on floor stands 6" (152.4mm) tall
Not available or required on units with EC fans
Cooling Type
A = Air-Cooled
D = Dual-Cooling, Air-Cooled
W = Water/Glycol
K = GLYCOOL
H = Dual-Cooling, Water-Cooled
Nominal kW
028, 035, 042, 053, 070, 077, 105
(8, 10, 12, 15, 20, 22, 30 tons)
Air Distribution
DS = Downflow Standard
VS = Upflow Standard
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
DS035AUA0EI****
Compressor
U - Semi-hermetic with four-step, R-407C
S - Scroll, R-407C
D - Digital Scroll, R-407C
Fan Type
0 = Centrifugal Fans
1 = EC Fans
Humidification
0 - None
I - Infrared
S - Steam Generating
Canister
Reheat Type
0 - None
E - 3-stage electric
S - SCR
Voltage
A - 460/3/60
B - 575/3/60
C - 208/3/60
D - 230/3/60
2 - 380/3/60
Factory Configuration
Number