User manual

Liebert DS Dimensions and Weights
15 Liebert
®
DS
Figure 10 Cabinet and floor planning dimensions—downflow, air-cooled, 53-77kW (15-22 ton), scroll
compressor models
Table 7 Weights for downflow, air-cooled, 53-77kW (15-22 ton), scroll compressor models
Coolant Type
Dry Weight, lb (kg)
053 070 077
Air Cooled 1920 (871) 1970 (894) 2020 (916)
Dual Coo 2100 (953) 2150 (975) 2200 (998)
Dimensions, in. (mm)
Air Cooled “A” 98 (2489) 98 (2489) 98 (2489)
Air Cooled “B” 97 (2464) 97 (2464) 97 (2464)
* Digital scroll compressor not available on 077 models.
Source: DPN000925, Rev. 2
33"
(838mm)
35"
(889mm)
A
76"
(1930mm)
2"
(51mm)
B
34"
(864mm)
Shaded area indicates a
recommended minimum
clearance for component access.
5"
(127mm)
3/4"
(19mm)
Bezels
24-5/8"
(619mm)
Opening
80"
(2032mm)
Second Refrigerant
Piping Entrance
AIR INLET OPENING
Opening
Secondary Entrance
Low-Volt Connections
Minimum required
for filter replacement
Secondary Entrance
High-Volt Connection(s)
TOP VIEW
FRONT VIEW
Notes: Filters are accessible
through top of unit only.
Downflow electrical
connections can be made
from top or bottom of unit.
DPN000925
Rev. 2
Digital scroll compressor
not available on 077 models.