User manual

Liebert DS Dimensions and Weights
Liebert
®
DS
16
Figure 11 Cabinet and floor planning dimensions—downflow, water/glycol/GLYCOOL, 53-77kW
(15-22 ton), all compressor models
Table 8 Weights for downflow, water/glycol/GLYCOOL, 53-77kW (15-22 ton), all compressor models
Compressor Type Coolant Type
Dry Weights, lb. (kg)
053 070 077
Semi-Hermetic
Water/Glycol 2650 (1205) 2700 (1228) 2750 (1250)
GLYCOOL/Dual-Cool 2830 (1287) 2880 (1310) 2930 (1332)
Scroll or Digital Scroll *
Water/Glycol 2220 (1010) 2270 (1032) 2320 (1055)
GLYCOOL/Dual-Cool 2400 (1091) 2450 (1114) 2500 (1137)
* Digital scroll compressor not available on 077 models.
Source: DPN000931, Rev. 4
Notes: Filters are accessible
through top of unit only.
Downflow electrical
connections can be made
from top or bottom of unit.
Shaded area indicates a
recommended minimum
clearance for component
access.
Required for
condenser cleanout
5"
(127mm)
34"
(864mm)
DPN000931
Rev. 4
76"
(1930mm)
TOP VIEW
Air Inlet Opening
Secondary Entrance
High-Volt Connection(s)
Secondary Entrance
Low-Volt Connections
80" (2032mm) Opening
35"
(889mm
24-5/8"
(625mm)
Opening
3/4" (20mm)
Bezels
Secondary Condenser
Fluid Piping Entrance
Condenser Cleanout Access
33"
(838mm)
24"
(610mm)
FRONT VIEW
2"
(51mm)
108" (2743mm)
109"
(2769mm)
Minimum
required
for filter
replacement
Digital scroll compressor
not available on 077 models.