Liebert DS Dimensions and Weights
19 Liebert
®
DS
Figure 14 Cabinet and floor planning dimensions—upflow, air-cooled 28-42kW (8-12 ton), semi-hermetic
compressor models
Table 11 Weight for upflow, air-cooled, 28-42kW (8-12 ton), semi-hermetic compressor models
Coolant Type Forward-Curved Fans EC Fans
Air-Cooled 1830 (830) 1680 (762)
Dual-Cool 1980 (898) 1830 (830)
Source: DPN001162, Rev. 2
DPN001162
Rev. 2
33"
(838mm)
35"
(889mm)
1-1/2"
(38mm)
86" (2184mm)
TOP VIEW
76"
(1930mm)
High-Volt Connection(s)
2"
(51mm)
85" (2159mm)
34"
(864mm)
24"
(610mm)
Minimum required
for blower replacement
Shaded area indicates a
recommended minimum
clearance for component
access.
FRONT VIEW
3/4"
(19mm)
Bezels
Low-Volt
Connection(s)
Alternate Refrigerant
Piping Entrance
Note: Front air return unit shown. For
rear return unit, in addition to front service
area shown, also include 25" (635mm) on
one side of unit for access to rear return
filter box. See DPN001196.
Note: Front air return unit shown. For rear
return unit, in addition to front service area
shown, also include 25" (635mm) on one side
of unit for access to rear return filter box.
See DPN001196, Figure 30.