Liebert DS Dimensions and Weights
21 Liebert
®
DS
Figure 16 Cabinet and floor planning dimensions—upflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton),
all compressor models
Table 13 Weights for upflow, water/glycol/GLYCOOL, 28-42kW (8-12 ton), all compressor models
Compressor Type
Coolant Type Forward-Curved Fans EC Fans
Semi-Hermetic
Water/Glycol 1980 (898) 1830 (830)
GLYCOOL/Dual-Cool 2130 (966) 1980 (898)
Scroll or Digital Scroll
Water/Glycol 1830 (830) 1680 (762)
GLYCOOL/Dual-Cool 1980 (898) 1830 (830)
Source: DPN001164, Rev. 2
DPN001164
Rev. 2
Alternate Condenser
Fluid Piping Entrance
3/4"
(19mm)
Bezels
24"
(610mm)
34"
(864mm)
85" (2159mm)
FRONT VIEW
Shaded area indicates a
recommended minimum
clearance for component
access.
2"
(51mm)
76"
(1930mm)
1-1/2"
(38mm)
TOP VIEW
86" (2184mm)
High-Volt Connection(s)
Condenser Cleanout Access
35"
(889mm)
33"
(838mm)
Minimum required
for blower replacement
Required for
condenser cleanout
Low-Volt Connection(s)
Note: Front air return unit shown. For
rear return unit, in addition to front service
area shown, also include 25" (635mm) on
one side of unit for access to rear return
filter box. See DPN001196.
Note: Front air return unit shown. For rear
return unit, in addition to front service area
shown, also include 25" (635mm) on one side
of unit for access to rear return filter box.
See DPN001196, Figure 30.