User manual

Liebert DS Dimensions and Weights
23 Liebert
®
DS
Figure 18 Cabinet and floor planning dimensions—upflow, air-cooled, 53-77kW (15-22 ton), scroll or
digital scroll compressor models
Table 15 Weight for upflow, air-cooled, 53-77kW (15-22 ton), scroll or digital scroll compressor models
Coolant Type Forward-Curved Fans EC Fans
Air-Cooled 2070 (939) 1900 (862)
Dual-Cool 2250 (1021) 2080 (943)
* Digital scroll compressor not available on 077 models.
Source: DPN001166, Rev. 2
33"
(838mm)
NOTE: Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
1-1/2"
(38mm)
TOP VIEW
High-Volt Connection(s)
Alternate Refrigerant
Piping Entrance
Low-Volt
Connection(s)
FRONT VIEW
DPN001166
Rev. 2
3/4"
(19mm) Bezels
35"
(889mm)
76"
(1930mm)
2"
(51mm)
98" (2489mm)
97" (2464mm)
Shaded area indicates a
recommended minimum
clearance for component access.
24"
(610mm)
34"
(864mm)
Minimum required
for blower replacement
Note: Front air return unit shown. For rear return unit, in addition to front
service area shown, also include 25" (635mm) on one side of unit for access
to rear return filter box. See DPN001196, Figure 30.
Digital scroll compressor not
available on 077 models.