User manual

Liebert DS Dimensions and Weights
Liebert
®
DS
24
Figure 19 Cabinet and floor planning dimensions—upflow, water/glycol/GLYCOOL, 53-77kW (15-22 ton),
all compressor models
Table 16 Weights for upflow, water/glycol/GLYCOOL, 53-77kW (15-22 ton), all compressor models
Fan Type
Semi-Hermetic Compressor Scroll or Digital Scroll Compressor
053 070, 077 053, 070, 077
Water/Glycol
GLYCOOL/
Dual-Cool Water/Glycol
GLYCOOL/
Dual-Cool Water/Glycol
GLYCOOL/
Dual-Cool
Forward-Curved 2650 (1205) 2830 (1287) 2800 (1270) 2980 (1352) 2370 (1075) 2550 (1157)
EC 2480 (1125) 2660 (1207) 2630 (1193) 2810 (1275) 2200 (998) 2380 (1080)
* Digital scroll compressor not available on 077 models.
33"
(838mm)
NOTE: Front air return unit shown. For rear return unit, in addition to front service
area shown, also include 25" (635mm) on one side of unit for access to rear
return filter box. See DPN001196.
1-1/2"
(38mm)
TOP VIEW
High-Volt Connection(s)
Alternate Condenser
Fluid Piping Entrance
Low-Volt
Connection(s)
FRONT VIEW
DPN001167
Rev. 2
3/4"
(19mm) Bezels
35"
(889mm)
76"
(1930mm)
2"
(51mm)
109" (2769mm)
108" (2743mm)
Shaded area indicates a
recommended minimum
clearance for component access.
24"
(610mm)
34"
(864mm)
Minimum required
for blower replacement
Required for
condenser cleanout
Condenser Cleanout Access
Note: Front air return unit shown. For rear return unit, in addition to front
service area shown, also include 25" (635mm) on one side of unit for access
to rear return filter box. See DPN001196, Figure 30.
Digital scroll compressor not
available on 077 models.