User manual

Liebert DS Dimensions and Weights
Liebert
®
DS
26
Figure 21 Cabinet and floor planning dimensions—upflow water/glycol/GLYCOOL 105kW (30 ton), all
models
Table 18 Weights—upflow water/glycol/GLYCOOL 105kW (30 ton), all models
Fan Type
Semi-Hermetic Compressor Standard Scroll Compressor
Air-Cooled Dual-Cool Air-Cooled Dual-Cool
Forward-Curved Fans
3370 (1529) 3700 (1678) 3250 (1474) 3580 (1624)
EC Fans
3130 (1420) 3460 (1569) 3010 (1365) 3340 (1515)
Digital scroll compressor not available on 105
Source: DPN001169, Rev. 1
DPN001169
Rev. 1
FRONT VIEW
TOP VIEW
High-Volt Connection(s)
Alternate Condenser
Fluid Piping Entrance
Alternate Refrigerant
Piping Entrance
Low-Volt Connection(s)
Shaded area indicates a
recommended minimum
clearance for component
access.
Minimum required
for blower replacement
Required for
condenser cleanout
Note: Front air return unit shown. For rear return unit, in addition to front
service area shown, also include 25" (635mm) on one side of unit
for access to rear return filter box. See DPN001196.
34"
(864mm)
24"
(610mm)
3/4"
(19mm)
Bezels
33"
(838mm)
35"
(889mm)
2"
(51mm)
76"
(1930mm)
1-1/2"
(38mm)
131" (3327mm)
132" (3353mm)
Note: Front air return unit shown. For rear return unit, in addition to
front service area shown, also include 25" (635mm) on one side of unit
for access to rear return filter box. See DPN001196, Figure 30.