User manual

Piping
Liebert
®
DS
88
9.2.1 Piping Guidelines—Air-Cooled Units
Indoor unit ships with a nitrogen holding charge; do not vent the evaporator until all refrigerant
piping is in place, ready for connection to the unit and condenser
Use copper piping with high temperature brazed joints
Isolate piping from building using vibration-isolating supports
Refer to Table 48 for piping sizes
Refer to condenser installation manual for charging information
Install traps on hot gas (discharge) lines at the base of vertical risers and every 25 feet (7.6m) of
vertical rise.
Consult factory if condenser is installed more than 15 feet (4.6m) below the evaporator
Consult factory if piping run exceeds 150 feet (46m) equivalent length
Keep piping clean and dry, especially on units with R-407C refrigerant
Avoid piping runs through noise-sensitive areas
Do not run piping directly in front of airstream
Refrigerant oil – do not mix oil types (see 13.10.1 - Compressor Oil)
Refer to ASHRAE Refrigeration Handbook for general, good-practice refrigeration piping.
Table 48 Recommended refrigerant line sizes - OD copper (inches)*
Standard Scroll Models (Non-Digital Scroll)
Model 028 035 042 053 070 077 105
Equivalent
Length
Hot
Gas
Line
Liquid
Line
Hot
Gas
Line
Liquid
Line
Hot
Gas
Line
Liquid
Line
Hot
Gas
Line
Liquid
Line
Hot
Gas
Line
Liquid
Line
Hot
Gas
Line
Liquid
Line
Hot
Gas
Line
Liquid
Line
50 ft (15m) 7/8 1/2 7/8 1/2 7/8 1/2 7/8 5/8 1-1/8 7/8 1-1/8 7/8 1-3/8 7/8
100 ft (30m) 7/8 5/8 7/8 5/8 7/8 5/8 1-1/8 7/8 1-1/8 7/8 1-1/8 7/8 1-3/8 7/8
150 ft (45 m) 7/8 5/8 7/8 5/8 7/8 5/8 1-1/8 7/8 1-1/8 7/8 1-1/8 7/8 1-3/8 1-1/8
4-Step Semi-Hermetic and Digital Scroll Models
Model 028 035 042 053 070 077 105
Equivalent
Length
Hot
Gas
Line
Liquid
Line
Hot
Gas
Line
Liquid
Line
Hot
Gas
Line
Liquid
Line
Hot
Gas
Line
Liquid
Line
Hot
Gas
Line
Liquid
Line
Hot
Gas
Line
Liquid
Line
Hot
Gas
Line
Liquid
Line
50 ft (15m) 3/4 1/2 3/4 1/2 7/8 5/8 7/8 7/8 1-1/8* 7/8 1-1/8 7/8 1-3/8 7/8
100 ft (30m) 3/4 5/8 7/8 5/8 7/8 5/8 1-1/8* 7/8 1-1/8 7/8 1-1/8 7/8 1-3/8 7/8
150 ft (45 m) 7/8 5/8 7/8 5/8 1-1/8* 5/8 1-1/8 7/8 1-1/8 7/8 1-1/8 7/8 1-3/8 1-1/8
* Downsize vertical riser one trade size (1-1/8" to 7/8")
* Digital scroll not available on 070 and 077 models.
Table 49 Indoor unit approximate refrigerant charge for R-407C
System Type Model R-407C Charge
per Circuit, lb (kg)
Air-Cooled
028, 035, 042 5.5 (2.5)
053, 070, 077 8.0 (3.6)
105 9.5 (4.3)
Water, Glycol/GLYCOOL
028, 035, 042 12.2 (5.6)
053, 070, 077 17.0 (7.8)
105 22.5 (10.3)