Specifications

9
3-5. UPS Setting
There are two parameters to set up the
UPS.
Parameter 1: It’s for program
alternatives. There are 8 programs to set
up. Refer to below table.
Parameter 2 is the setting option or value
for each program.
z
01: Output voltage setting
Interface Setting
Parameter 2: Output voltage setting
You may choose the following output voltage in parameter
2:
208:
presents output voltage is 208Vac
220:
presents output voltage is 220Vac
230:
presents output voltage is 230Vac
240:
presents output voltage is 240Vac
z
02: Frequency Converter enable/disable
Interface Setting
Parameter 2:
Enable or disable converter mode. You may
choose the following two options:
CF ENA:
converter mode enable
CF DIS:
converter mode disable
z
03: Output frequency setting
Interface Setting
Parameter 2: Output frequency setting.
You may set the initial frequency on battery mode:
BAT 50:
presents output frequency is 50Hz
BAT 60:
presents output frequency is 60Hz
If converter mode is enabled, you may choose the following
output frequency:
CF 50:
presents output frequency is 50Hz
CF 60:
presents output frequency is 60Hz