Specifications

4
Step 2: UPS output connection
There two kinds of outputs: programmable outlets and general outlets. Please connect non-critical
devices to the programmable outlets and critical devices to the general outlets. During power failure,
you may extend the backup time to critical devices by setting shorter backup time for non-critical
devices.
Step 3: Communication connection
Communication port:
USB port RS-232 port Intell
igent slot
To allow for unattended UPS shutdown/start-up and status monitoring, connect the communication
cable one end to the USB/RS-232 port and the other to the communication port of your PC. With the
monitoring software installed, you can schedule UPS shutdown/start-up and monitor UPS status
through PC.
The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card. When installing
either SNMP or AS400 card in the UPS, it will provide advanced communication and monitoring
options.
PS. USB port and RS-232 port can’t work at the same time.
Step 4: Network connection
Network/Fax/Phone surge port
Connect a single modem/phone/fax line into surge-protected “IN” outlet on the back panel of the
UPS unit. Connect from “OUT” outlet to the equipment with another modem/fax/phone line cable.
Step 5: Disable and enable EPO function
Keep the pin 1 and pin 2 closed for UPS normal operation. To activate EPO function, cut the wire
between pin 1 and pin 2.
Step 6: Turn on the UPS
Press the ON/Mute button on the front panel for two seconds to power on the UPS.
Note: The battery charges fully during the first five hours of normal operation. Do not expect full
battery run capability during this initial charge period.
It’s in closed status for UPS
normal operation.