User manual

Service Menu Parameters
94
Figure 87 System/network setup screen—Unit, page 2 of 2
Monitoring Protocol—Selects the monitoring protocol. Velocity V4 is the factory default that will
provide communication to the Liebert IntelliSlot housing. IGMNet will activate the 77/78 terminals
for communication to the Liebert SiteLink(-E). Liebert Hironet is only used on Liebert HPM units.
IP Address—Contains the network address of the display. This address must be unique on the
network.
Netmask—Not currently used.
Gateway—Not currently used.
MAC—Unique hardware identifier of the Ethernet device.
U2U Protocol—This parameter is always set to GBP.
U2U Address—Unique identifier for each unit on the network. Display addresses range from 33 to
64. Each display on the U2U network must have a different U2U address.
U2U Group—Creates zones or groups within a U2U network. Once a group number is selected, the
display will see only devices with the same group number. The group number can be changed to view
other devices in different groups.
Bootloader Variables—Indicates if there has been a change to the boot loader since it was last
loaded. This parameter should only be activated by an authorized service person.
Attention: any changes done on these parameters
must be followed by a 'Save+Reboot' command.
SYSTEM/NETWORK SETUP (page 2 of 2) UNIT 01
S834
S835
S836
S837
S838
S839
S840
S841
S842
S843
S844
PASSWORD (Actual Level 3) ????
Monitoring Protocol Velocity
IP Address 192 .168.254.001
Netmask 255.255.255.000
Gateway 0:000:000:000
MAC 00:00:68:1E:8E:92
U2U Protocol GBP
U2U Address 1
U2U Group 1
Bootloader Variables Changed No
Static RAM OK No