Service Menu Parameters
96
Figure 89 Options setup, page 2 of 5
Humidification Enabled—Enables or disables humidification.
Infrared Flush Rate—Shows the amount of makeup water supplied to an infrared humidifier as a
percentage of the humidifier capacity. This value can be set from 110-500% (default is 150%). Higher
flush rates reduce mineral deposit buildup in the humidifier pan.
Humidifier Steam Rate (Liebert HPM and Liebert PeX only)—Reduces humidifier capacity to be a
percentage of nominal humidifier capacity on units with variable capacity steam bottle humidifiers.
Humidifier Control—Used for Liebert HPM and Liebert PeX units only.
Humidifier Bottle Flush Time—Used for Liebert HPM and Liebert PeX units only.
Humidifier Bottle Manual Flush—Used for Liebert HPM and Liebert PeX units only.
Dehumidification Enabled—Selects whether the compressor and / or valve will be used to
dehumidify when the humidity is above setpoint.
Auto Restart Enabled—Restarts the unit after a power cycle when set to “Yes.” When this
parameter is set to “No,” the unit will not restart (Turn On) after a power cycle.
Single Unit Auto Restart—Sets a time delay for the unit to restart when the Auto Restart Enabled
is set to “Yes”. The delay begins once the boot process has completed. This parameter allows units to
be staggered On to reduce the amount of simultaneous power consumption after a loss of power.
On-Off Enabled—Disables the power button on the front of the display. The default configuration is
“On”.
OPTIONS SETUP (page 2 of 5)
to change parameter
to confirm
to select parameter
for next/previous unit
then
PASSWORD (Actual Level 3) ????
Humidification Enabled Yes
Infrared Flush Rate 150%
Humidifier Steam Rate %
Humidifier Control
Humidifier Bottle Flush Time sec
Humidifier Bottle Manual Flush
Dehum Enabled / Dehum Fan Cntl No
Auto Restart Enabled Yes
Single Unit Auto Restart 5sec
On-Off Enabled Yes
UNIT 01
S412
S413
S414
S415
S416
S417
S418
S419
S420
S421
S422