User manual

Operation
33
The valve pulse and cooling filter timer can be adjusted to prevent oscillating around the supply
setpoint and still allow for rapid valve adjustments to compensate for heat load changes. Contact
your local Liebert service personnel for adjustments.
Return Compensation begins to increase the supply air setpoint when the return air decreases
below the return air setpoint.
Example
Setting the return compensation value in the Service, Setpoints menu to 5°F (2.7°C) will
increase the supply setpoint from 50°F to 55°F (10°C to12.8°C) when the return temperature is
at the low limit of the proportional band.
3.8 Liebert Smart Aisle Control
Liebert Smart Aisle Control allows the Liebert iCOM to manage airflow and cooling capacity
independently. This control mode allows the unit to adjust the airflow based on the cold aisle
temperature and the cooling output based on the discharge air temperature.
The Liebert Smart Aisle Control focuses on the inlet temperature to the racks. The Liebert Smart
Aisle Control also manages each component independently to manage the energy usage to provide the
correct amount of cooling. As the environment changes, the Liebert iCOM will adjust the airflow and
heat rejection based on the sensor readings at the discharge air temperature of the unit and the cold
aisle temperature.
The Liebert Smart Aisle Control also will automatically adjust cooling based on the configuration of
the cold aisle. The control can automatically adjust fan speed and cooling capacity when the cold aisle
configuration is changed. This includes no containment, end containment and total containment of
the cold aisle.
Currently, the Liebert Smart Aisle Control is limited to chilled water units with variable speed fans
and one cold aisle sensor per unit.
Figure 26 Equipment layout for Liebert Smart Aisle Control
3.8.1 Hardware Setup
The Liebert Smart Aisle Control requires:
A temperature/humidity sensor in the cold aisle and connected to the Liebert iCOM via CAN bus.
This can be done by:
Moving the return temperature sensor from the cooling unit to the cold aisle with a longer
CAN Bus cable
OR BY
Obtaining a remote temperature sensor and addressing it to operate as the return
temperature sensor.
An additional supply temperature sensor placed under the raised floor.
CANbus
Supply Sensor (Cooling Capacity)
Supply Sensor (Cooling Capacity)
Server Rack Server Rack
Temp/Hum Sensor
(Fanspeed Control)
iCOM
Opening
Water Valve
Speed Control
M1
CRAC Unit
CANbus
iCOM
Water Valve
Opening
Speed Control
M1
CRAC Unit