User manual
External Communication—Building Management Systems, Liebert SiteScan
®
54
6.0 EXTERNAL COMMUNICATION—BUILDING MANAGEMENT SYSTEMS, LIEBERT
SITESCAN
®
Liebert iCOM is capable of communicating with external monitoring systems, such as Building
Management Systems (BMS), Network Monitoring Systems (NMS), Liebert's SiteScan
®
Web system
and others.
Each Liebert iCOM-controlled cooling unit is equipped with Liebert IntelliSlot plug-in slots for use
with optional communication cards:
• Ethernet Web/SNMP Card
• RS-485 Modbus Card
The hot-swappable plug-in cards provide interfaces supporting open protocols, including Modbus,
HTTP (Web) and SNMP. See the Liebert Web site for the latest supported protocols, Modbus
reference information and SNMP MIBs: www.liebert.com
An alternate, limited method of communicating with an existing Liebert SiteScan Web monitoring
system is via twisted-pair cables connected to terminals 77 and 78 on the cooling unit terminal strip.
To use this method, the Liebert IntelliSlot power supply connection to P65 on the Liebert iCOM I/O
board must be unplugged, and the factory-supplied 77-78 cable must be connected to P65 (follow
Liebert SiteScan instructions for further connections). The appropriate Liebert iCOM control
parameters must be configured to utilize the terminals.
Liebert iCOM software versions PA1.04.022.STD and older, which shipped before to November 2010,
will support Velocity V3.
The older Velocity V3 cards will become obsolete with the advent of the Velocity V4 protocol and the
newer Liebert IntelliSlot cards that communicate with this protocol. The newer cards are compatible
with the older Liebert IntelliSlot cards’ Modbus mapping and data.
NOTE
Liebert SiteScan will be limited to legacy parameters when communicating via
Terminals 77 and 78.
Table 15 Liebert IntelliSlot card compatibility
Software Version
Card
Compatibility Protocol Supported
PA1.04.033.STD—Velocity V4
IS-485L Modbus RTU 485
IS-WEBL SMTP, SNMP, SMS, HTTP
IS-485EXI
Liebert SiteLink-E communication card
(supports enhanced data set for Liebert iCOM)
IS-IPBML Modbus IP
— * BacNet available soon
PA1.04.022.STD and Older—Velocity V3
OC485-LBDS Modbus RTU 485 / IGMNet Extended
ISWEB-LBDS SNMP , HTTP
The newer communication cards support the latest information available through Liebert iCOM. Previous Liebert IntelliSlot cards
should be used for legacy information.