User manual
Service Menu Parameters
68
Figure 52 Setpoints screen, page 6 of 6
SCR Control Type—Sets the control type for the SCR reheats. If set to “Standard,” then the reheats
will modulate when the temperature is below setpoint based on the control settings. If this parameter
is set to “Tight” control then one compressor will be locked on and the reheats will modulate to offset
the cooling capacity.
Start Compressor 1 / 2 at—Sets the activation point of the compressor. This parameter can be used
when set to “Tight” control.
Stop Compressor 1 / 2 at—Sets the deactivation point of the compressor. This parameter can be
used when set to “Tight” control.
Compressor 1 / 2 stop delay—Sets the delay when the stop compressor setpoint is met.
Cycle time—Set at the factory and should be changed only by an authorized Liebert representative.
SCR Factor—Set at the factory and should be changed only by an authorized Liebert representative.
Unit Diary—Large Display Only
Shows all entered program changes and maintenance performed on the unit.
Table 16 Unit diary parameters
Function
Range
Imperial (metric)
Large Display Small Display
Page 1 of 1
Text entered with iST
(Liebert iCOM Service Tool)
N/A -
SETPOINTS (pg 6 of 6)
to change parameter
to confirm
to select parameter
for next/previous unit
then
UNIT 01
PASSWORD (Actual Level 0) ????
SCR Control Type
Start Compressor 1 At %
Stop Compressor 1 At %
Compressor 1 Stop Delay min
Start Compressor 2 At %
Stop Compressor 2 At %
Compressor 2 Stop Delay min
Cycle Time sec
SCR Factor
Actual SCR Request %