User manual
Service Menu Parameters
75
Figure 63 Diagnostics/service mode screen, page 2 of 8
Manual Mode—Places the Liebert iCOM in manual mode. This is the initial setting necessary to
activate any of the following items.
Motor(s)—Starts the unit’s main fan. The main fan must be On before any of the following overrides
can be activated.
Compressor 1—Turns on Compressor 1 and selects the mode of compressor operation. The choices
are RUN, EVACUATE and CHARGE.
Compressor 1 Capacity—Enable Compressor 1 Cycle Ramp.
Compressor 1 Cycle Ramp—Select the capacity the compressor should run at. The range is
0to100%.
Compressor 1 LLSV—Control the liquid line solenoid valve for Compressor 1.
Compressor 2—Turns on Compressor 2 and selects the mode of compressor operation. The choices
are RUN, EVACUATE and CHARGE
Compressor 2 Capacity—Enables Compressor 2 Cycle Ramp.
Compressor 2 Cycle Ramp—Selects the capacity the compressor should run at. The range is
0to100%.
Compressor 2 LLSV—Controls the liquid line solenoid valve for Compressor 2.
DIAGNOSTICS / SERVICE MODE (page 2 of 8)
to change parameter
to confirm
to select parameter
for next/previous unit
then
PASSWORD (Actual Level 0) ????
Manual Mode No
Motors On
Compressor 1 Run Off
Compressor 1 Capacity Off
Compressor 1 Cycle Ramp 0%
Compressor 1 LLSV Off
Compressor 2
Compressor 2 Capacity
Compressor 2 Cycle Ramp %
Compressor 2 LLSV
S312
S313
S314
S315
S316
S317
S318
S319
S320
S321
S322
UNIT 01