Service Menu Parameters
75
Figure 63 Diagnostics/service mode screen, page 2 of 8
Manual Mode—Places the Liebert iCOM in manual mode. This is the initial setting necessary to
activate any of the following items.
Motor(s)—Starts the unit’s main fan. The main fan must be On before any of the following overrides
can be activated.
Compressor 1—Turns on Compressor 1 and selects the mode of compressor operation. The choices
are RUN, EVACUATE and CHARGE.
Compressor 1 Capacity—Enable Compressor 1 Cycle Ramp.
Compressor 1 Cycle Ramp—Select the capacity the compressor should run at. The range is
0to100%.
Compressor 1 LLSV—Control the liquid line solenoid valve for Compressor 1.
Compressor 2—Turns on Compressor 2 and selects the mode of compressor operation. The choices
are RUN, EVACUATE and CHARGE
Compressor 2 Capacity—Enables Compressor 2 Cycle Ramp.
Compressor 2 Cycle Ramp—Selects the capacity the compressor should run at. The range is
0to100%.
Compressor 2 LLSV—Controls the liquid line solenoid valve for Compressor 2.