Service Menu Parameters
76
Figure 64 Diagnostics/service mode screen, page 3 of 8
Electric Heat 1 (or HG/HW)—Activates Stage 1 of the unit’s reheat system.
Electric Heat 2 (or HG/HW)—Activates Stage 2 of the unit’s reheat system.
Electric Heat 3 (or HG/HW)—Activates Stage 3 of the unit’s reheat system.
SCR Heat—Specifies the pulse width the heating system should run at on units using silicon
controlled rectifier type reheat.
Dehumidification Output—Activates the dehumidification cycle.
Humidifier Fill—Activates the humidifier water source solenoid valve, which fills the humidifier
pan or canister with water.
Humidifier—Activates the humidifier system in its entirety.
Humidifier Drain—Activates the humidifier drain solenoid, allowing water to drain from the
canister if the unit is equipped with an optional the steam generating humidifier.
Humidifier Current—Shows the amount of AC amperes the humidifier is consuming if the unit is
equipped with an optional the steam generating humidifier.
DIAGNOSTICS / SERVICE MODE (page 3 of 8)
to change parameter
to confirm
to select parameter
for next/previous unit
then
PASSWORD (Actual Level 0) ????
Electric Heat 1 (or HG/HW) Off
Electric Heat 2 (or E.Heat 1) Off
Electric Heat 3 (or E.Heat 2) Off
SCR Heat %
Dehumidification Output Off
Humidifier Fill Off
Humidifier Off
Humidifier Drain
Humidifier Current 0.00A
S323
S324
S325
S326
S327
S328
S329
S330
S331
S332
S333
UNIT 01