Service Menu Parameters
76
Figure 64 Diagnostics/service mode screen, page 3 of 8
Electric Heat 1 (or HG/HW)—Activates Stage 1 of the unit’s reheat system.
Electric Heat 2 (or HG/HW)—Activates Stage 2 of the unit’s reheat system.
Electric Heat 3 (or HG/HW)—Activates Stage 3 of the unit’s reheat system.
SCR Heat—Specifies the pulse width the heating system should run at on units using silicon
controlled rectifier type reheat.
Dehumidification OutputActivates the dehumidification cycle.
Humidifier Fill—Activates the humidifier water source solenoid valve, which fills the humidifier
pan or canister with water.
Humidifier—Activates the humidifier system in its entirety.
Humidifier Drain—Activates the humidifier drain solenoid, allowing water to drain from the
canister if the unit is equipped with an optional the steam generating humidifier.
Humidifier Current—Shows the amount of AC amperes the humidifier is consuming if the unit is
equipped with an optional the steam generating humidifier.