Service Menu Parameters
82
Figure 70 Set alarms screen, page 1 of 8
Return Sensor Alarms—Enables and disables the return temperature and humidity sensor alarms.
Factory default is set to enable.
High Return Temperature—Sets the threshold temperature when a return high temperature
alarm will occur.
Low Return Temperature—Sets the threshold temperature when a return low temperature alarm
will occur.
High Return Humidity—Sets the threshold humidity when a return high humidity alarm will
occur.
Low Return Humidity—Sets the threshold humidity when a return low humidity alarm will occur.
Sensor A Alarms—Enables or disables the alarms associated with Sensor A if the unit is equipped
with the optional temperature / humidity sensor.
High Temperature Sensor A—Sets the threshold temperature when a Sensor A high temperature
alarm will occur.
Low Temperature Sensor A—Sets the threshold temperature when a Sensor A low temperature
alarm will occur.
High Humidity Sensor A—Sets the threshold humidity when a Sensor A humidity alarm will
occur.
Low Humidity Sensor A—Sets the threshold humidity when a Sensor A low humidity alarm will
occur.
SET ALARMS (page 1 of 8)
to change parameter
to confirm
to select parameter
for next/previous unit
then
PASSWORD (Actual Level 0) ????
Return Sensor Alarms Enable
High Return Temperature 80°F
Low Return Temperature 65°F
High Return Humidity 60%
Low Return Humidity 40%
Sensor A Alarms Disable
High Temperature Sensor A °F
Low Temperature Sensor A °F
High Humidity Sensor A %
Low Humidity Sensor A %