User manual
Service Menu Parameters
84
Figure 72 Set alarms screen, page 3 of 8
Customer Input 1, 2, 3 & 4—Select the device and operation of the customer inputs. Each event
reflects a different alarm and possible action to the unit. Refer to Table 7 for a description of
selectable options.
Customer Input 1, 2, 3 & 4 active when—Select whether the input is a normally closed or
normally closed input.
WARNING ACTIVATES ALARM RELAY—Sets the alarm relay (K3) to activate when a warning
occurs.
Water Alarm Shuts Unit Down—Turn the unit Off if a water alarm occurs.
Set Alarm Screens, Pages 4-8
The Set Alarm Screens, pages 4 through 8 (Figures 73 through 77) permit setting the operation of an
active alarm. Each event can be enabled or disabled and can be set to operate as an alarm, warning or
message. The delay is the time the control waits before reporting the event.
Alarm: Annunciates the buzzer, triggers a monitoring event, triggers the alarm relay and flashes
the red LED on the display
Warning: Annunciates the buzzer, triggers a monitoring event, shows the event in the event
viewer / front display and flashes the red LED on the display.
Message: Shows the event in the event viewer and on the front display.
Delay—The delay selection for each alarm.
EN-DIS—The enable / disable selection for each alarm provides the ability to individually select the
alarms that will or will not activate when the alarm condition occurs.
Type—Sets the type of action for each event listed. There are three different types of events: Alarm,
Warning and Message. When an event is triggered and the type is set to “Alarm,” then the light and
buzzer on the display will activate, an event will be written to the event log and the (K3) alarm relay
will close. If the type is set to “Warning,” then the light and buzzer on the display will activate, an
event will be written to the event log and the (K3) alarm relay can be configured to close or provide no
reaction. If the type is set to “Message,” then the event is only written to the event log.
SET ALARMS (page 3 of 8) UNIT 01
S223
S224
S225
S226
S227
S228
S229
S230
S231
S232
S233
to confirm
for next/previous unit
then
to select parameter
to change parameter
PASSWORD (Actual Level 0) ????
Customer Input 1 Water Alarm
Customer Input 1 active when Closed
WARNING ACTIVATES ALARM RELAY Yes
Water Alarm Shuts Unit Down Yes
Reset Disabled Alarms No