User manual
Service Menu Parameters
86
Figure 75 Set alarms screen, page 6 of 8
Figure 76 Set alarms screen, page 7 of 8
SET ALARMS (page 6 of 8)
PASSWORD (Actual Level 0) ????
DELAY EN-DIS TYPE
WORKING HRS EXCEEDED 0 ENABLE WRN
SMOKE DETECTED 2 ENABLE ALM
WATER UNDER FLOOR 2 ENABLE ALM
COND PUMP-HIGH WATER 2 ENABLE ALM
LOSS OF FLOW 5 ENABLE ALM
STBY PUMP ON 2 ENABLE ALM
STANDBY UNIT ON 2 ENABLE ALM
HUMIDIFIER PROBLEM 2 ENABLE ALM
NO CONNECTION w/Unit1 ENABLE WRN
UNIT X DISCONNECTED ENABLE WRN
LOSS OF POWER DISAB WRN
S260
S261
S262
S263
S264
S265
S266
S267
S268
S269
S270
S271
S272
UNIT 01
SET ALARMS (page 7 of 8)
PASSWORD (Actual Level 0) ????
DELAY EN-DIS TYPE
CUSTOMER INPUT 1 2 ENABLE ALM
CUSTOMER INPUT 2 2 ENABLE ALM
CUSTOMER INPUT 3 2 ENABLE ALM
CUSTOMER INPUT 4 2 ENABLE ALM
CALL SERVICE 2 ENABLE ALM
HIGH TEMPERATURE 2 ENABLE ALM
LOSS OF AIR BLOWER 1 2 ENABLE ALM
REHEAT LOCKOUT 2 ENABLE WRN
HUMIDIFIER LOCKOUT 2 ENABLE WRN
FC LOCKOUT 2 ENABLE WRN
COMPRESSOR LOCKOUT 2 ENABLE WRN
S273
S274
S275
S276
S277
S278
S279
S280
S281
S282
S283
S284
S285
UNIT 01