User manual
Service Menu Parameters
87
Figure 77 Set alarms screen, page 8 of 8
Figure 78 iCOM-DO overview and override screen, page 1 of 3
Liebert iCOM-DO—Shows the connection status of a Liebert iCOM-DO card. It displays “connected”
when a Liebert iCOM-DO card has been set up and connected to the Liebert iCOM via the CAN bus.
Override—Permits manual testing the Liebert iCOM-DO by activating each output on the following
screen.
SET ALARMS (page 8 of 8)
PASSWORD (Actual Level 0) ????
DELAY EN-DIS TYPE
COMP 1 SHORT CYCLE 0 ENABLE WRN
COMP 2 SHORT CYCLE 0 ENABLE WRN
NO POWER 0 DISAB WRN
CONDENSER 1 FAILURE 0 ENABLE WRN
CONDENSER 2 FAILURE 0 ENABLE WRN
EC FAN FAULT 5 ENABLE ALM
HIGH SUP TEMP 30 DISAB WRN
LOW SUP TEMP 30 DISAB WRN
S286
S287
S288
S289
S290
S291
S292
S293
S294
S295
S296
S297
S298
UNIT 01
iCOM-DO Overview and Override (pg 1 of 3)
to change parameter
to confirm
to select parameter
for next/previous unit
then
UNIT 01
PASSWORD (Actual Level 3) ????
iCOM-DO #0 connected
Override #0 no
S720
S721
S722
S723
S724
S725
S726
S727
S728
S729
S730