User manual

Service Menu Parameters
89
Figure 81 Sensor calibration setup screen, page 1 of 3
Return Temperature—Adjusts the return temperature reading from the actual sensor to
compensate for any error of the sensor or to match other sensors in the room.
Calibrated Return Temperature—Shows the adjusted temperature value of the return sensor.
This value is the actual sensor reading (+ or -) the offset “Return Temperature”.
Return Humidity—Adjusts the return humidity reading from the actual sensor to compensate for
any error of the sensor or to match other sensors in the room.
Calibrated Return Humidity—Shows the adjusted humidity value of the return sensor. This value
is the actual sensor reading (+ or -) the offset “Return Humidity”.
Digital Scroll 1 NTC—Adjusts the digital scroll 1 NTC reading from the actual sensor to
compensate for any error or drift of the sensor.
Calibrated Digital Scroll 1 NTC—Shows the adjusted Digital Scroll 1 NTC sensor value. This
value is the actual sensor reading (+ or -) the offset “Digital Scroll 1 NTC”.
Digital Scroll 2 NTC—Adjusts the digital scroll 1 NTC reading from the actual sensor to
compensate for any error or drift of the sensor.
Calibrated Digital Scroll 2 NTC—Shows the adjusted Digital Scroll 1 NTC sensor value. This
value is the actual sensor reading (+ or -) the offset “Digital Scroll 1 NTC.”