Service Menu Parameters
90
Figure 82 Sensor calibration/setup screen, page 2 of 3
Optional Sensor A, B and C—Adjusts the reading from the actual sensor to compensate for any
error of the sensor or to match other sensors in the room.
Calibrated Optional Sensor A, B and C—Shows the adjusted value of the sensor. This value is the
actual sensor reading (+ or -) the offset.
Optional Sensor B and C Type—Currently supports only the “TH” Temperature/Humidity sensor
type.
Figure 83 Sensor calibration/setup screen, page 3 of 3
Freecool Sensor PTC or NTC—Currently supports only the NTC selection.
Freecool Sensor—Adjusts the free-cooling temperature reading from the actual sensor to
compensate for any sensor error or to match other sensors in the room.
Calibrated Freecool Sensor—Shows the adjusted temperature value of the free-cooling sensor.
This value is the actual sensor reading (+ or -) the offset “Freecool Sensor”.
Supply Sensor—Adjusts the supply temperature reading from the actual sensor to compensate for
any error of the sensor or to match other sensors in the room.
Calibrated Supply Sensor—Shows the adjusted temperature value of the supply sensor. This value
is the actual sensor reading (+ or -) the offset “Supply Sensor”.