User manual
Service Menu Parameters
90
Figure 82 Sensor calibration/setup screen, page 2 of 3
Optional Sensor A, B and C—Adjusts the reading from the actual sensor to compensate for any
error of the sensor or to match other sensors in the room.
Calibrated Optional Sensor A, B and C—Shows the adjusted value of the sensor. This value is the
actual sensor reading (+ or -) the offset.
Optional Sensor B and C Type—Currently supports only the “TH” Temperature/Humidity sensor
type.
Figure 83 Sensor calibration/setup screen, page 3 of 3
Freecool Sensor PTC or NTC—Currently supports only the NTC selection.
Freecool Sensor—Adjusts the free-cooling temperature reading from the actual sensor to
compensate for any sensor error or to match other sensors in the room.
Calibrated Freecool Sensor—Shows the adjusted temperature value of the free-cooling sensor.
This value is the actual sensor reading (+ or -) the offset “Freecool Sensor”.
Supply Sensor—Adjusts the supply temperature reading from the actual sensor to compensate for
any error of the sensor or to match other sensors in the room.
Calibrated Supply Sensor—Shows the adjusted temperature value of the supply sensor. This value
is the actual sensor reading (+ or -) the offset “Supply Sensor”.
SENSOR CALIBRATION/SETUP (page 2 of 3)
to change parameter
to confirm
to select parameter
for next/previous unit
then
PASSWORD (Actual Level 3) ????
Optional Sensor A 1 +0°F
Calibrated Optional Sensor A 1 72°F
Optional Sensor A 2 +0.0 %
Calibrated Optional Sensor A 2 49.5 %
Optional Sensor B Type TT
Optional Sensor B 1 +0°F
Calibrated Optional Sensor B 1 °F
Optional Sensor B 2 +0.0°F
Calibrated Optional Sensor B 2 °F
Optional Sensor C Type TT
UNIT 01
S612
S613
S614
S615
S616
S617
S618
S619
S620
S621
S622
SENSOR CALIBRATION/SETUP (page 3 of 3)
to change parameter
to confirm
to select parameter
for next/previous unit
then
PASSWORD (Actual Level 3) ????
Freecool Sensor PTC or NTC NTC
Freecool Sensor +0°F
Calibrated Freecool Sensor °F
Supply Sensor PTC or NTC NTC
Supply Sensor +0.0°F
Calibrated Supply Sensor 51.2°F
Optional Sensor C 1 +0°F
Calibrated Optional Sensor C 1 °F
Optional Sensor C 2 +0.0°F
Calibrated Optional Sensor C 2 °F
UNIT 01
S623
S624
S625
S626
S627
S628
S629
S630
S631
S632
S633