Service Menu Parameters
91
Figure 84 System/network setup screen—System, page 1 of 2 (large display only)
Number of Connected Units—Sets the number of units that will be viewable from the large display
and will participate on the unit to unit network.
Teamwork Mode—Selects which teamwork mode to use within a selected group. Teamwork modes
are described in section 4.0 of this manual.
Configuration Safe—Saves or loads configuration settings for the display that have been modified
from the factory defaults to an internal file that can be downloaded / uploaded using the Liebert
iCOM Service Tool. Selecting “Save” will write the settings to the internal storage file and selecting
“Load” will write the settings from the internal storage file to the application software. The internal
file is updated every 12 hours automatically.
Network Safe—Saves or loads network settings for the display that have been modified from the
factory defaults to an internal file that can be downloaded/uploaded using the Liebert iCOM Service
Tool. Selecting “Save” will write the settings to the internal storage file. Selecting “Load” will write
the settings from the internal storage file to the application software.
SW Version—Contains the application software version loaded onto the Liebert iCOM display.
SYSTEM/NETWORK SETUP (pg 1 of 2)
to change parameter
to confirm
to select parameter
for next/previous unit
then
SYSTEM
S801
S802
S803
S804
S805
S806
S807
S808
S809
S810
S811
PASSWORD (Actual Level 3) ????
Number of Connected Units 1
Teamwork Mode No
Configuration Safe OK No
Network Safe OK No
SW Version PAB 1.04.010.T14