Service Menu Parameters
93
Figure 86 System/network setup screen—Unit, page 1 of 2
Monitoring Address—Sets the address used by the Liebert Intellislot
®
cards. This is set to 3 at the
factory and should not be changed.
Monitoring Timeout / Handshake—Used with a building management system to verify
communication between the Liebert iCOM and the BMS has not been lost. If the amount of time
specified in this parameter elapses before the BMS writes a new value, then an alarm will occur “BMS
TIMEOUT” and the temperature setpoint will revert to the backup setpoint and the fan speed “if
equipped” will change to 100%. To disable this feature, write a zero to this parameter when it is active.
Unit Name—A label to identify the unit from the local or remote display. This label will show at the
top right of every screen that has monitoring or configuration of that unit.
Configuration Safe—Saves or loads configuration settings for the control board that have been
modified from the factory defaults to an internal file that can be downloaded / uploaded using the
Liebert iCOM Service Tool. Selecting “Save” will write the settings to the internal storage file and
selecting “Load” will write the settings from the internal storage file to the application software. The
internal file is updated every 12 hours automatically.
Network Safe—Saves or loads network settings for the control board that have been modified from
the factory defaults to an internal file that can be downloaded / uploaded using the Liebert iCOM
Service Tool. Selecting “Save” will write the settings to the internal storage file and selecting “Load”
will write the settings from the internal storage file to the application software.
SW Version—Contains the application software version loaded onto the Liebert iCOM control board.
SYSTEM/NETWORK SETUP (pg 1 of 2)
to change parameter
to confirm
to select parameter
for next/previous unit
then
UNIT 01
S823
S824
S825
S826
S827
S828
S829
S830
S831
S832
S833
PASSWORD (Actual Level 3) ????
Monitoring Address 3
Monitoring Timeout /Handshake No/ 0
Unit Name Unit
Configuration Safe Changed No
Network Safe OK No
SW Version PAL 1.04.010.T14