User manual
Installing a Liebert iCOM Unit-to-Unit Network
95 Liebert
®
iCOM
®
Figure 79 U2U network setup diagram
NOTE
The first three octets of the units’ IP addresses must match for proper communication. In the
illustration above, these are the matching octets: 192.168.254
Network
Switch
Liebert Cooling Unit
with Small Liebert
iCOM Display
Liebert Cooling Unit
with Small Liebert
iCOM Display
Liebert Cooling Unit
with Large Liebert
iCOM Display
Display Service/Network
Liebert iCom Display Menu
IP Address: 192.168.254.001
U2U Address: 33
Group #: 1
---------------------------------------
Display Service/Network
Liebert Cooling Unit
Control Board Menu
IP Address: 192.168.001.002
U2U Address: 1
Group #: 1
Display Service/Network
Liebert Cooling Unit
Control Board Menu
IP Address: 192.168.254.003
U2U Address: 2
Group #: 1
Display Service/Network
Liebert Cooling Unit
Control Board Menu
IP Address: 192.168.254.004
U2U Address: 3
Group #: 1