Service Menu Parameters
Liebert
®
iCOM
®
160
Figure 149 Sensor calibration/setup screen, page 6 of 7
S657 DP Transducer is Connected to—Sets the analog output that will be used for the differential
pressure transducer. This parameter is selectable from None, Ana In 1, Ana In 2, Ana In 3 and
Ana In 4. The factory default is none.
S658 DP Transducer is Setup in—Sets the unit of measure that will be used for the differential
pressure transducer. This parameter is selectable in inWC or PA. The factory default is PA.
S659 DP Transducer Low—Sets the unit of measure that will be used for the low differential
pressure transducer. This parameter is selectable from 0-9.999 inWC. The factory default is 0.000
inWC.
S660 DP Transducer High—Sets the unit of measure that will be used for the high differential
pressure transducer. This parameter is selectable from 0-9.999 inWC. The factory default is 2.005
inWC.
S661 Number of EC Fans—Sets the unit of number of EC fans. This parameter is selectable
between 1 and 5. The factory default is 3.
S662 Inlet Ring K-Value—Sets the inlet ring K-Value. This parameter is selectable between 1 and
999. The factory default is 480.
S664 Results:—Read-only string that describes S665 through S668.
S665 DP Transducer Low—Shows the status of the low differential pressure transducer in both
inWC and Pa after it’s setup at S659.
S666 DP Transducer High—Shows the status of the high differential pressure transducer in both
inWC and Pa after it's setup at S660.
S667 Actual DP Signal—Shows the actual differential pressure transducer percentage.
S668 Calculated Airflow—Shows the calculated airflow based on the low, high, number of EC fans
and the Inlet Ring K-Value settings.