Figure 29 Second cooling source and two-step compressorized cooling
Minimum Chilled Water Temperature—This feature allows the user to select a minimum chilled
water temperature to prevent simultaneous operation of the chilled water (free-cooling) and
compressor(s) on units factory-programmed to operate both sources simultaneously. This feature is
enabled in the Service menu under Setpoints, parameter Minimum CW Temp.
If the fluid temperature sensed is below the Minimum CW Temp Value, (Service Menu, Setpoints),
and the Delta T (Temperature Difference) Between Room and Glycol (see 3.3.1 - Differential
Temperatures / Controls (Comparator Circuit) is satisfied, the control will operate ONLY the
chilled water for cooling. The compressor(s) is locked out. If cooling is not achieved at this time (i.e.,
loss of chilled water flow), the control will override this setting and activate a compressor(s). When
this happens, a free-cooling lockout for one hour event is produced. Free-cooling will not resume until
one hour has elapsed.
If the fluid temperature is above the minimum CW value, the control will operate the chilled water
(free-cooling) and compressor(s) simultaneously if needed. If the Minimum CW Temp is disabled, the
control may operate both sources as load requires.
7571 72 73 7470
Increasing Temperature
Cool 2
On
Cool 1
On
+ 100%
Cooling
Valve 100%
Open
Valve
Closed
½ Dead-
band
76 77 78 79
+ 200%
Cooling
0%
Cooling
2nd
Source
Comp
½ Proportional Band ½ Proportional Band
Band 1: 2
nd
Source Band 2: Compressors
Temp Setpoint: 70°F
Proportional Band: 8°F
Deadband: 2°F