User manual

Operation
51 Liebert
®
iCOM
®
Figure 46 Dehumidification and reheat control bands
Low Limit 1 and Low Limit 2 are used to avoid overcooling a room during dehumidification. When a
low limit is reached, a compressor or the liquid cooling source that is used for dehumidification is
disabled. It is re-enabled when the return air temperature rises. The Low Limit 1 and 2 settings are
in the Service menu under Setpoints.
Low Limit 1: Low Limit 1 will disable one of two compressors for dehumidification. If only one
compressor is set for dehumidification, or if the dehumidification source is chilled water, this limit
will not be visible and will be inactive.
Low Limit 2: Low Limit 2 will disable both compressors for dehumidification. This limit will also
stop dehumidification in single compressor units and in chilled water units.
The limits become active when the return air temperature drops below a temperature value equal to
the sum of the temperature setpoint plus the value set on Low Limit 1 and 2 (the Low Limit settings
are negative values).
A dehumidification source is deactivated if the return air temperature drops below the Deactivation
Temperature, as in this example:
Temperature Setpoint: 70°F (21.1°C)
Low Limit Value: -7°F (-3.8°C)
Deactivation Temperature: 63°F (17.2°C)
NOTE
If a cooling unit is equipped with SCR reheat and the SCR Control Type parameter is set to
Tight mode, then Low Limit 2 will be ignored, see 3.5 - Temperature Control—Reheat.
Dehum Reheat Prop Band
-100%
-Temp
33% 33% 33%
Step 3 Step 2
Step 3 on
Step 3 off
Step 2 on
Step 2 off
Step 1 on
Step 1 off
0%
Dehum/ Reheat
Setpoint
0%
Heater
Deadband
Step 1
Dehum Reheat Prop Band
0%
Dehum/ Reheat
Setpoint
-100%
-Temp
33% 33% 33%
Step 3 Step 2
Step 3 on
Step 3 off
Step 2 on
Step 2 off
Step 1 on
Step 1 off
Step 1