User manual
Teamwork
83 Liebert
®
iCOM
®
Figure 70 DIP switches in 2T sensors
Set 2T Rack Sensor Identities - DIP Switch Settings
1. Confirm that the DIP switches are set correctly for all 2T sensors.
2. Apply numbered stickers to the sensor housings, corresponding to sensor chain position.
3. Based on the sensor number, use the included DIP switch tool to set the DIP switches according to
Table 15. If the settings are difficult to make through the opening in the housing or if the hole is
not present, open the case by removing the three Phillips-head screws. Reassemble housing once
the settings are made.
Figure 71 Setting 2T Sensor DIP Switches
Table 15 DIP switch settings
2T Sensor #
DIP switch Position
12345678
1 Off Off On Off On Off Off Off
2 On Off On Off On Off Off Off
3 Off On On Off On Off Off Off
4 On On On Off On Off Off Off
5 Off Off Off On On Off Off Off
6 On Off Off On On Off Off Off
7 Off On Off On On Off Off Off
8 On On Off On On Off Off Off
9 Off Off On On On Off Off Off
10 On Off On On On Off Off Off
NOTE
Use included DIP switch tool (or similar tool). DO NOT insert any metal object
into the sensor case.
Switch Up = ON
Switch Down = OFF
Non-conductive
DIP switch tool
2T sensor housing DIP switch hole
2T sensor housing case opened