User manual

Operation
15
Once the compressor is locked off, it will not come back on until the HP Alarm Counters (Service
Menu, Diagnostics) are reset to 0. Setting the counter to 0 will auto-reset the alarm without the need
of pressing the reset button on the display. Even if the pressure in the system drops below the alarm
point, the compressor will remain off until the system is reset.
3.1.3 Compressor Timing—Units With Two Compressors
To help maximize the life of your compressor(s), there is a start-to-next start delay for each single
compressor.
A Minimum ON time and a Minimum Off time may be selected in the Advanced menu (minimum
three minutes for single phase compressors). Consult the factory on how to modify the Minimum ON
and OFF time settings.
3.1.4 Compressor Sequencing
Compressor Sequencing parameter (Service Menu, Options Setup) is intended to maintain equal run
times between compressors. This setting has three selection possibilities:
Always use Compressor 1 as lead compressor
Always use Compressor 2 as lead compressor
Auto:
First priority: if the safety timings are acceptable for only one compressor, then it is the next
to be started/stopped.
If both compressors are off: the one with fewer working hours is the next to start.
If both compressors are in operation: the one that has been operating longer since the last
start is the next to be stopped.
NOTE
If the unit is equipped with manual reset high head pressure switches, or if the auto reset
high head pressure switches don’t reset, the compressor will not be turned back on, but there
will be a 30-second delay from when the high head pressure situation occurs and when the
alarm is annunciated.
NOTE
The Auto setting attempts to maintain equal run times between compressors.