User manual

User Menu Parameters
44
7.0 USER MENU PARAMETERS
User menus report general cooling unit operations and status. The password for the user menu is
1490.
The iCOM control firmware is being updated constantly. As a result, the User menu parameter tables
in this manual may be slightly different than what is shown on your cooling unit's display. Contact
your local Emerson office for the latest iCOM User manual updates.
Spare Part List—Large Display Only
Displays the various Liebert part numbers for all parts in the cooling unit to simplify ordering
replacement parts.
Table 13 Setpoints parameters
Function
Read/
Write
Range
Metric (Imperial)
Default
Setting
Large Display Small Display
Page 1 of 1
Password PASSWORD W - -
Temperature Setpoint TEMP SET W 5-40°C (41-104°F) 23°C (73°F)
Humidity Setpoint HUM SET W 20-80% 50%
Humidity Control Type HUM CTRL W Relative, Compensated, Predictive Predictive
Supply Limit SUP LIM W Enabled, Disabled Disabled
Supply Limit Temp Value SUP TEMP W 5-25°C (41-77°F) 5°C (41°F)
Table 14 Spare part list parameters—large display only
Function
Read/
Write
Range
Metric (Imperial)
Default
Setting
Large Display Small Display
Page 1 of 1
List of parts N/A R - -
Table 15 Event log parameters
Function
Read/
Write
Range
Metric (Imperial)
Default
Setting
Large Display Small Display
Page 1 of 1
Last 400 events Last 400 events R - -
°C / °F
% RH
SET
EVENT
LOG