User manual
User Menu Parameters
45
Table 16 Graphics parameters
Function
Read/
Write
Range
Metric (Imperial)
Default
Setting
Large Display Small Display
Page 1 of 1
System temperature time scale N/A W
8,32 min; 1,12,24 hours,
2,4,8,16 days
24 hours
System temperature graph height N/A W ±3-20°C (±5-36°F) 6°C (11°F)
System humidity time scale N/A W
8,32 min; 1,12,24 hours,
2,4,8,16 days
24 hours
System humidity graph height N/A W ±10-30% 25%
Unit temperature time scale
UNIT TEMPERATURE TIME
SCALE
W
8,32 min; 1,12,24 hours,
2,4,8,16 days
24 hours
Unit temperature graph height
UNIT TEMPERATURE
GRAPH HEIGHT
W ±3-20°C (±5-36°F) 6°C(11°F)
Unit humidity time scale UNIT HUMIDITY TIME SCALE W
8,32 min; 1,12,24 hours,
2,4,8,16 days
24 hours
Unit humidity graph height
UNIT HUMIDITY GRAPH
HEIGHT
W ±10-30% 25%
Table 17 View network parameters—large display only*
Function
Read/
Write
Range
Metric (Imperial)
Default
Setting
Large Display Small Display
Page 1 of 1
Status Unit 1—32 N/A R - -
* Permits viewing all units connected in a network. Viewable on a large display only.
Table 18 Set alarms parameters
Function
Read/
Write
Range
Metric (Imperial)
Default
Setting
Large Display Small Display
Page 1 of 1
Password PASSWORD W - -
Return Sensor Alarms RTN SNSR W Enabled, Disabled Enabled
High Return Temperature HI TEMP W 1-99°C (34-210°F) 27°C (80°F)
Low Return Temperature LO TEMP W 1-99°C (34-210°F) 18°C (65°F)
High Return Humidity HI HUM W 1-99% 60%
Low Return Humidity LOW HUM W 1-99% 40%
Sensor A Alarms SENSOR A W Enabled, Disabled Disabled
High Temperature Sensor A HI TEMP A W 1-99°C (34-210°F) 32°C (90°F)
Low Temperature Sensor A LO TEMP A W 1-99°C (34-210°F) 13°C (55°F)
High Humidity Sensor A HI HUM A W 1-99% 70%
Low Humidity Sensor A LO HUM A W 1-99% 30%
SET
ALARMS