User manual
Service Menu Parameters
51
See 3.6.1 - Calculation of Next Maintenance and Diagnostics for details on these menus.
Table 27 Standby settings / lead-lag parameters
Function
Read/
Write
Range
Metric (Imperial)
Default
Setting
Large Display Small Display
Page 1 of 1
Password PASSWORD W - -
Number of Standby Units #STANDBY W 0-32 0
Rotation Frequency ROTATION W
No, Daily,
Every Mo-Tu-We-Th-Fr-Sa-Su;
(Monthly) M-Mo, M-Tu, M-We,
M-Th, M-Fr, M-Sa, M-Su
No
Rotate At (hour) ROT HOUR W 0-23 0
Rotate At (minute) ROT MIN W 0-59 0
Rotate By ROT BY W 1-8 1
Perform One Rotation DO ROT W No, Yes -
Cascade Units CASCADE W No, Yes, Cooling, Cool/Heat No
Start all Standby Units
by HT
STBY HT W No, Yes No
Table 28 Maintenance / wellness settings parameters
Function
Read/
Write
Range
Metric (Imperial)
Default
Setting
Large Display Small Display
Basic Settings (Page 1 of 8)
Password PASSWORD W - -
Maintenance Frequency Per Year FREQ/YR W 0-12 per year 1
Max Bonus BONUS W 0-12 0
Max Penalty PENALTY W 0-12 0
Last Maintenance LAST PM W Date -
Service Engineer SERVICE W Name -
Confirm PM CONFIRM W No, Yes -
Calculated Next Maintenance NEXT PM W Date -
Motor Settings (Page 2 of 8)
Password PASSWORD W - -
Number of Starts STARTS W 0-32000 -
Run Hours RUN HRS W 0-32000 -
Average Run Time AVG RUN W 0-999 min -
Starts per Day Best BEST W 1-240 1
Starts per Day Worst WORST W 1-240 24
Number of Alarms ALARMS W 0-32000 -
Actual Bonus BONUS R 0-12 -
WELLNESS