User manual

Service Menu Parameters
56
Page 7of 7
Status Humidifier Problem HUM PROB R OK, Act -
Status DT2 (Glycol/Room) DT2 R OK, Act -
Status DT3 (Room/Setpoint) DT3 R OK, Act -
Status Min CW MIN CW R OK, Act -
LWD Value R -
Table 30 Set alarms parameters
Function
Read/
Write
Range
Metric (Imperial)
Default
Setting
Large Display Small Display
Page 1 of 7
Password PASSWORD W - -
Return Sensor Alarms RTN SNSR W Enabled, Disabled Enabled
High Return Temperature HI TEMP W 1-99°C (34-210°F) 27°C (80°F)
Low Return Temperature LO TEMP W 1-99°C (34-210°F) 18°C (65°F)
High Return Humidity HI HUM W 1-99% 60%
Low Return Humidity LOW HUM W 1-99% 40%
Sensor A Alarms SENSOR A W Enabled, Disabled Disabled
High Temperature Sensor A HI TEMPA W 1-99°C (34-210°F) 32°C (90°F)
Low Temperature Sensor A LO TEMPA W 1-99°C (34-210°F) 13°C (55°F)
High Humidity Sensor A HI HUM A W 1-99% 70%
Low Humidity Sensor A LO HUM A W 1-99% 30%
Table 29 Diagnostics / service mode parameters (continued)
Function
Read/
Write
Range
Metric (Imperial)
Default
Setting
Large Display Small Display
SERVICE
SET