User manual

Service Menu Parameters
58
Table 31 Set alarms parameters (continued)
Function
Read/
Write
Delay
(Default)
ENABLE - DISAB
(Default)
Alarm Type
(Default)
Large Display Small Display
Page 3 of 7
Password PASSWORD W - - -
Main Fan Overload FOL W 0-9999 sec (5) Enable, Disab (Enable) ALM,WRN,MSG (ALM)
Loss Of Airflow LOA W 0-9999 sec (3) Enable, Disab (Enable) ALM,WRN,MSG (ALM)
Clogged Filters CF W 0-9999 sec (2) Enable, Disab (Enable) ALM,WRN,MSG (WRN)
High Room Temp HRT W 0-9999 sec (30) Enable, Disab (Enable) WRN
Low Room Temp LRT W 0-9999 sec (30) Enable, Disab (Enable) WRN
High Room Hum HRH W 0-9999 sec (30) Enable, Disab (Enable) WRN
Low Room Hum LRH W 0-9999 sec (30) Enable, Disab (Enable) WRN
High Temp Sensor A HTA W 0-9999 sec (30) Enable, Disab (Enable) WRN
Low Temp Sensor A LTA W 0-9999 sec (30) Enable, Disab (Enable) WRN
High Hum Sensor A HHA W 0-9999 sec (30) Enable, Disab (Enable) WRN
Low Hum Sensor A LHA W 0-9999 sec (30) Enable, Disab (Enable) WRN
Page 4 of 7
Password PASSWORD W - - -
Comp 1 Overload OL1 W internal Enable, Disab (Enable) ALM,WRN,MSG (ALM)
Comp 2 Overload OL2 W internal Enable, Disab (Enable) ALM,WRN,MSG (ALM)
Comp 1 High Pressure HP1 W internal Enable, Disab (Enable) ALM,WRN,MSG (ALM)
Comp 2 High Pressure HP2 W internal Enable, Disab (Enable) ALM,WRN,MSG (ALM)
Comp 1 Low Pressure LP1 W internal Enable, Disab (Enable) ALM,WRN,MSG (ALM)
Comp 2 Low Pressure LP2 W internal Enable, Disab (Enable) ALM,WRN,MSG (ALM)
Comp 1 Pumpdown Fail PD1 W internal Enable, Disab (Enable) ALM,WRN,MSG (ALM)
Comp 2 Pumpdown Fail PD2 W internal Enable, Disab (Enable) ALM,WRN,MSG (ALM)
Dig Scroll1 High Temp HT1 W internal Enable, Disab (Enable) ALM,WRN,MSG (ALM)
Dig Scroll2 High Temp HT2 W internal Enable, Disab (Enable) ALM,WRN,MSG (ALM)
EL Heat High Temp EHO W 0-9999 sec (5) Enable, Disab (Enable) ALM,WRN,MSG (WRN)
Page 5 of 7
Password PASSWORD W - - -
Working Hrs Exceeded WHE W 0-9999 sec (0) Enable, Disab (Enable) WRN
Smoke Detected SMO W 0-9999 sec (2) Enable, Disab (Enable) ALM,WRN,MSG (ALM)
Water Under Floor WUF W 0-9999 sec (2) Enable, Disab (Enable) ALM,WRN,MSG (ALM)
Cond Pump-high Water CPH W 0-9999 sec (2) Enable, Disab (Enable) ALM,WRN,MSG (ALM)
Loss Of Flow LOF W 0-9999 sec (2) Enable, Disab (Enable) ALM,WRN,MSG (ALM)
Stby Glycol Pump On SGP W 0-9999 sec (2) Enable, Disab (Enable) ALM,WRN,MSG (ALM)
Standby Unit On STB W 0-9999 sec (2) Enable, Disab (Enable) ALM,WRN,MSG (ALM)
Humidifier Problem HUP W 0-9999 sec (2) Enable, Disab (Enable) ALM,WRN,MSG (ALM)
No Connection w/Unit1 NOC W internal Enable, Disab (Enable) WRN
Unit X Disconnected - W internal Enable, Disab (Enable) WRN
Loss Of Power LOP - - Enable, Disab (Enable) ALM,WRN,MSG (ALM)
SET
ALARMS