User manual

Service Menu Parameters
59
Page 6 of 7
Password PASSWORD W - - -
Customer Input 1 CI1 W 0-9999 sec (2) Enable, Disab (Enable) ALM,WRN,MSG (ALM)
Customer Input 2 CI2 W 0-9999 sec (2) Enable, Disab (Enable) ALM,WRN,MSG (ALM)
Customer Input 3 CI3 W 0-9999 sec (2) Enable, Disab (Enable) ALM,WRN,MSG (ALM)
Customer Input 4 CI4 W 0-9999 sec (2) Enable, Disab (Enable) ALM,WRN,MSG (ALM)
Call Service CS W 0-9999 sec (2) Enable, Disab (Enable) ALM,WRN,MSG (ALM)
High Temperature HTD W 0-9999 sec (2) Enable, Disab (Enable) ALM,WRN,MSG (ALM)
Loss of Air Blower 1 LB1 W 0-9999 sec (2) Enable, Disab (Enable) ALM,WRN,MSG (ALM)
Reheat Lockout RL W 0-9999 sec (2) Enable, Disab (Enable) ALM,WRN,MSG (ALM)
Humidifier Lockout HL W 0-9999 sec (2) Enable, Disab (Enable) ALM,WRN,MSG (ALM)
FC Lockout FCL W 0-9999 sec (2) Enable, Disab (Enable) ALM,WRN,MSG (ALM)
Compressor(S) Lockout CL W 0-9999 sec (2) Enable, Disab (Enable) ALM,WRN,MSG (ALM)
Page 7 of 7
Password PASSWORD W - - -
Comp 1 Short Cycle SC1 W 0-9999 sec (0) Enable, Disab (Enable) ALM,WRN,MSG (ALM)
Comp 2 Short Cycle SC2 W 0-9999 sec (0) Enable, Disab (Enable) ALM,WRN,MSG (ALM)
No Power NP W 0-9999 sec (0) Enable, Disab (Enable) ALM,WRN,MSG (ALM)
Condenser 1 Failure CF 1 W 0-9999 sec (5) Enable, Disab (Enable) ALM,WRN,MSG (ALM)
Condenser 2 Failure CF 2 W 0-9999 sec (5) Enable, Disab (Enable) ALM,WRN,MSG (ALM)
Table 31 Set alarms parameters (continued)
Function
Read/
Write
Delay
(Default)
ENABLE - DISAB
(Default)
Alarm Type
(Default)
Large Display Small Display
SET
ALARMS