Service Menu Parameters
63
Table 35 Options setup parameters
Function
Read/
Write
Range
Metric (Imperial)
Default
Setting
Large Display Small Display
Page 1 of 3
Password PASSWORD W - -
Compressor Sequence COMP SEQ R 1, 2, auto Auto
Low Pressure Alarm Delay LP DELAY W 0-5 min 3
Actual LP1 Pressure LP1 ACT R
-10.0 - 50.0 bar
(-145.0 - 725.0 psi)
-
Actual LP2 Pressure LP2 ACT R
-10.0 - 50.0 bar
(-145.0 - 725.0 psi)
-
Electric Stages EL HEAT W 0, 1, 2, 3 1
Hot Water Heat On/Off HW HEAT W No, Yes No
Total Heat Stages ALL HEAT R 0, 1, 2, 3 -
LWD Connected LWDconn W No, Yes No
3P Actuator Runtime 3P RUN W 30-500 sec 165 sec
3P Actuator Direction 3P DIR W Direct, Reverse Direct
Page 2 of 3
Password PASSWORD W - -
Humidification Enabled HUM ENAB W No, Yes Yes
Infrared Flush Rate IR FLUSH W 110-500% 150%
Humidifier Steam Rate R 0-100% -
Humidifier Bottle Flush Time HumFlush W 5-30 sec 5
Humidifier Bottle Manual Flush ManFlush W Yes, No No
Dehumidification Enabled DEHUM EN W No, Yes Yes
Auto Restart Enabled W No, Yes Yes
Single Unit Auto Restart RESTART W 0-999 sec 5
On-Off Enabled ONOFF EN W Yes, No Yes
Page 3 of 3
Password PASSWORD W - -
CW Flush CW FLUSH W 0-99 hours 0
Freecooling Flush FC FLUSH W 0-99 hours 0
Hot Water Flush HW FLUSH W 0-99 hours 0