User's Manual

User Menu Parameters
Liebert
®
iCOM
®
116
Figure 99 Display setup screen, page 2
U414 Additional Readouts—Selects whether fluid flow is displayed in the unit view.
U415 Show Supply Temp @ Unit Off—Hides or shows the supply air temperature when the unit is
in monitoring Off, display Off, in remote shutdown or in standby mode. This feature is typically used
by BMS integrators to prevent nuisance high supply temperature alarms while the unit is not cooling.
U416 Show U2U Numbers—Hides or shows the U2U number to the right of the unit name.
7.6 User-Total Run Hours Menu Screens
Total Run Hours displays the cumulative hours a particular component has been operating and the
limit placed on the hours the component may operate.
Each main component of the unit has its own run hours counter and a threshold. The actual run
hours can be reset to 0 by selecting the counter by pressing Enter, and then pressing the Down arrow
key. The thresholds can be set the same way.
Figure 100 Total run hours screen
NOTE
The password needs to be entered in any other screen because this screen does not contain a
password entry line.