User's Manual
Service Menu Parameters
Liebert
®
iCOM
®
158
Figure 150 Sensor calibration/setup screen, page 2 of 12
Optional Sensor A and B—Adjusts the reading from the actual sensor to compensate for any error
of the sensor or to match other sensors in the room.
Calibrated Optional Sensor A and B—Shows the adjusted value of the sensor. This value is the
actual sensor reading (+ or -) the offset.
Optional Sensor B & C Type—Read-only parameter, Liebert iCOM automatically detects the type
of sensor connected and displays the sensor type here.
Figure 151 Sensor calibration/setup screen, page 3 of 12
S624 Freecool Sensor PTC or NTC—Currently supports only the NTC selection.
S625 Freecool Sensor—Adjusts the free-cooling temperature reading from the actual sensor to
compensate for any sensor error or to match other sensors in the room.
S626 Calibrated Freecool Sensor—Shows the adjusted temperature value of the free-cooling
sensor. This value is the actual sensor reading (+ or -) the offset Freecool Sensor.
S627 Supply/Return Sensor PTC or NTC—Supports only the NTC selection.