User's Manual

Inspection and Installation
17 Liebert
®
MC
Figure 14 Lifting condensers with one, two, three or four fans
3.6 Mounting the Condenser
The condenser must be installed so that it is level within 1/2" (13mm) to ensure proper refrigerant
flow. For roof installation, mount the condenser on suitable curbs or other supports; follow all local
and national codes. Secure the legs to the mounting surface using a field-supplied 1/2" (13mm)
diameter bolt in each of the two 1/2" x 1" (12.7x25.4mm) obround holes in each leg. See Figures 3
through 7 for anchor dimensions.
Spreader Bars
(must be wider
than the
Liebert MC to
prevent crushing
force)
Straps go through holes in legs
on one-fan and two-fan units
Straps or chains go through
eyebolts on three-fan and
four-fan units
308111
Pg. 3, Rev. 1