REPLACING THE BATTERY
Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and required precautions.
When replacing batteries, replace with the same type and size battery.
To replace the battery:
1. Turn off all connected loads, then turn off the UPS and unplug the input
power cord. (Batteries are NOT hot-swappable.)
2. Carefully lay the UPS on its left side, as shown in the diagram.
3. Use a #1 Phillips head screwdriver to remove the four screws from the
right-side cover, then pull up the right-side cover and remove it.
4. Remove the black wire from the negative (-) terminal and the red wire from
the positive (+) terminal.
5. Gently remove the battery from the UPS.
Attention: Risk of Electric Shock.
6. Verify that the replacement battery matches the dimensions and battery
specification.
7. Connect the battery leads to the new battery. Be sure to reconnect the red
wire to the positive (+) terminal and the black wire to the negative (-)
terminal.
Note: Small sparks may occur at the battery connectors during
reconnection. Take care not to short-circuit the positive and negative
battery terminals while replacing the battery.
8. Place the battery in the UPS.
9. Ensure correct alignment of front panel, then reattach the right-side cover.
Evenly tighten the four screws from Step 3. (Do NOT over tighten screws)
Dispose of the old battery properly at an appropriate recycling facility.
TROUBLESHOOTING
If the UPS detects a fault, consult the table below for possible causes and solutions. For further assistance, please contact your local Emerson Network Power representative.
SPECIFICATIONS
!
CAUTION
Do not dispose of batteries in a fire. The batteries may explode.
!
CAUTION
Do not open or mutilate batteries. Released electrolyte is harmful to the skin and eyes. It is toxic.
This product is designed for 120V equipment.
Fault Possible Causes Solutions
Utility power is normal, but LED 1 is not illuminated.
The UPS may not be turned on.
The power cord may not be connected properly.
The upstream input circuit breaker may be tripped.
Press the On/Off button to turn on the UPS.
Connect the power cord securely into a wall outlet.
Reset the input circuit breaker.
LED 1 flashes (green) every 3 seconds, but there is
no output power.
Battery voltage may be too low. Recharge the UPS for 8 hours.
Alarm buzzer beeps continuously although utility
power is normal.
The UPS may be overloaded (check LED 2). Disconnect some equipment from the UPS.
UPS does not provide expected backup time. The UPS battery reached end of life. Replace the internal battery.
The UPS is on and connected to input power, but fails
to operate properly.
Utility power may be outside the unit’s operating range.
If utility power is normal, try reconnecting input
power and restarting the UPS.
Model Number PSP350MT3-120U PSP500MT3-120U
Capacity (VA/W) 350/210 500/300
Net Weight, lb. (kg) 6.4 (2.9) 8.8 (4.0)
Shipping Weight, lb. (kg) 7.7 (3.5) 10.1 (4.6)
Dimensions - W x D x H, in. (mm) 3.4 x 8.5 x 9.9 (87 x 215 x 251)
Input Voltage 84-140VAC
Frequency 50/60Hz ±5Hz
Output Voltage (Utility Power Normal) Typical 84-140VAC
Output Voltage (Battery Operation) 120VAC ±5%
On-Battery Wave Form Stepped sinewave
VRLA Battery Type - VDC x Ah x Quantity 12V x 5Ah x 1 12V x 7.2Ah x 1
Typical Recharge Time 6-8 hours to 90%
Battery Run Time* - Full Load 3-5 minutes
Battery Run Time* - Half Load 10 minutes
Audible and Visual Audible alarm / LED
Backup Outlets NEMA 5-15R (3)
Surge Outlets NEMA 5-15R (1)
Operating Temperature, °F (°C) 32 to 104 (0 to 40)
Storage Temperature, °F (°C) 5 to 104 (-15 to 40)
Operating / Storage Relative Humidity 0%-90%, non-condensing
EMI Classification FCC Part 15 Class B
Agency**
Safety UL 1778, c-UL Listed
EMC
FCC Part 15 Class B
IEC 61000-4-2 Electrostatic discharge
IEC 61000-4-3 Radiated E-RFI fields
IEC 61000-4-4 Fast E transients
IEC 61000-4-5 Surges/Lightning
IEC 61000-4-6 Conducted RFI
ANSI C62.41 Category A Level 3 (surges)
Transportation ISTA Procedure 1A Certification
* Battery run time may vary depending on load.
** The Liebert PSP is compliant with the Restriction of Hazardous Substances Directive (ROHS),
prohibiting use of six hazardous materials manufacturing of electronics, including lead-free solder.
Step 1
Steps 2 and 3
ATTENTION:
Risk of
Electric Shock