4.12 Liebert XDV Standard Features
• Micro Channel Heat Exchanger—The Liebert XDV unit includes one all-aluminum micro
channel heat exchanger.
• Dual IEC Power Cords and Power Inlets—The Liebert 115V, 60Hz Liebert XDV unit is sup-
plied with two detachable, 10 ft (3m) power cords that attach to two IEC power inlets in the rear
of the unit. Each power cord has a NEMA 5-15P (IEC 320-C14) plug at the opposite end. The Lie-
bert 230V, 60/50 Hz Liebert XDV unit is supplied with two non-detachable 10 ft (3m) power cords.
This feature allows the unit to be powered by two separate power sources.
• Dual Air Inlets—The Liebert XDV unit can be configured to allow air to enter from the rear
grille or the bottom of the unit.
• Dual Fans—Airflow is provided by two fans on the front of the unit. Dual switches—Controls on
the front of the unit permit the use of one fan or both fans.
• Foundation Mounting—There are two 1/4-20 cage nuts located on the underside of unit which
allow direct attachment to any Liebert Foundation cabinet, bolts provided with Liebert XDV unit.
• Mounting Clips for Non-Liebert Cabinets—The Liebert XDV unit is supplied with mounting
clips that allow attachment to a non-Liebert cabinet (Some drilling may be required).
4.13 Optional Features—Liebert XDV
• Refrigerant Pre-Charge—The Liebert XDV can be precharged with refrigerant. The unit will
have the one-shot fittings and will be pressurized. The one-shot Liebert XD Flex Piping will also
be precharged with refrigerant.
• External Mounting Brackets—The Liebert XDV can be suspended from the overhead building
structure. The external mounting brackets are ship-loose items.
• Field-Installed Flexible Piping (for use with prefabricated piping assemblies)—Field-installed
flexible piping kits are available in lengths of 4, 6, 8 and 10 feet (1.2, 1.8, 2.4 and 3 meters). Con-
nection style to the unit end may be straight or 90 degrees with one-shot or removable connec-
tions. Flex pipes with one-shot connections will have pressurized R134a. Flex pipes with
removable connections will have a low pressure nitrogen charge Connection to the prefabricated
piping assembly is with a threaded coupler. For information on acquiring the correct kit for your
installation, refer to DPN000781, available from Liebert by calling 1-800-LIEBERT and from
your local Emerson Network Power representative.
• Smart Module—Liebert XDV smart modules allow remote shutdown, fan failure alarms and auto-
matically switching the second fan On and Off. This saves energy by permitting the unit to run
with one fan and switching on a second fan when the temperature requires both fans for cooling.
For electrical connection details, refer to the Liebert XDV user manual, SL-16626, available on
the Liebert Web site: www.liebert.com