Specifications

Liebert XD Cooling Modules—Liebert XDCF, Liebert XDH, Liebert XDO, Liebert XDR and Liebert XDV
58
4.12 Liebert XDV Standard Features
Micro Channel Heat Exchanger—The Liebert XDV unit includes one all-aluminum micro
channel heat exchanger.
Dual IEC Power Cords and Power Inlets—The Liebert 115V, 60Hz Liebert XDV unit is sup-
plied with two detachable, 10 ft (3m) power cords that attach to two IEC power inlets in the rear
of the unit. Each power cord has a NEMA 5-15P (IEC 320-C14) plug at the opposite end. The Lie-
bert 230V, 60/50 Hz Liebert XDV unit is supplied with two non-detachable 10 ft (3m) power cords.
This feature allows the unit to be powered by two separate power sources.
Dual Air Inlets—The Liebert XDV unit can be configured to allow air to enter from the rear
grille or the bottom of the unit.
Dual Fans—Airflow is provided by two fans on the front of the unit. Dual switches—Controls on
the front of the unit permit the use of one fan or both fans.
Foundation Mounting—There are two 1/4-20 cage nuts located on the underside of unit which
allow direct attachment to any Liebert Foundation cabinet, bolts provided with Liebert XDV unit.
Mounting Clips for Non-Liebert Cabinets—The Liebert XDV unit is supplied with mounting
clips that allow attachment to a non-Liebert cabinet (Some drilling may be required).
4.13 Optional Features—Liebert XDV
Refrigerant Pre-Charge—The Liebert XDV can be precharged with refrigerant. The unit will
have the one-shot fittings and will be pressurized. The one-shot Liebert XD Flex Piping will also
be precharged with refrigerant.
External Mounting Brackets—The Liebert XDV can be suspended from the overhead building
structure. The external mounting brackets are ship-loose items.
Field-Installed Flexible Piping (for use with prefabricated piping assemblies)—Field-installed
flexible piping kits are available in lengths of 4, 6, 8 and 10 feet (1.2, 1.8, 2.4 and 3 meters). Con-
nection style to the unit end may be straight or 90 degrees with one-shot or removable connec-
tions. Flex pipes with one-shot connections will have pressurized R134a. Flex pipes with
removable connections will have a low pressure nitrogen charge Connection to the prefabricated
piping assembly is with a threaded coupler. For information on acquiring the correct kit for your
installation, refer to DPN000781, available from Liebert by calling 1-800-LIEBERT and from
your local Emerson Network Power representative.
Smart Module—Liebert XDV smart modules allow remote shutdown, fan failure alarms and auto-
matically switching the second fan On and Off. This saves energy by permitting the unit to run
with one fan and switching on a second fan when the temperature requires both fans for cooling.
For electrical connection details, refer to the Liebert XDV user manual, SL-16626, available on
the Liebert Web site: www.liebert.com