MESA® SOLE Outdoor Electronic Enclosure Description and Installation Part Number 631-205-105 Version C, August 2009
Copyright 2009, Emerson Network Power, Energy Systems, North America, Inc. All rights reserved. Any unauthorized reproduction or transmission without the prior consent of Emerson Network Power, Energy Systems, North America, Inc. is prohibited. This document is the property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy Systems, North America, Inc.
Emerson Network Power Wireline Products 631-205-105 Version B, March 2009 Table of Contents 1. ABOUT THIS DOCUMENT 1 2. CABINET DESCRIPTION 2 2.1 Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 2.2 Physical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 2.3 Standards Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
631-205-105 Version B, March 2009 Emerson Network Power Wireline Products 10.
Emerson Network Power Wireline Products 631-205-105 Version B, March 2009 List of Figures Fig. 1 MESA® SOLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 Fig. 2 MESA® SOLE Exploded View . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 Fig. 3 MESA® SOLE Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Fig. 4 1/ -turn 4 security bolt . . . . . . . . .
Emerson Network Power Wireline Products 631-205-105 Version C, August 2009 MESA® SOLE OUTDOOR ELECTRONIC ENCLOSURE DESCRIPTION AND INSTALLATION 1. ABOUT THIS DOCUMENT 1.1 Purpose - This practice provides a description and installation instructions for the MESA® SOLE (Modular Electronic Sealed Architecture) cabinet. See Fig. 1. 1.2 Reason For Reissue - Practice revised to add additional clarification to Fig. 9, Concrete Pad Template Diagram. 1.
631-205-105 Version C, August 2009 Emerson Network Power Wireline Products 2. CABINET DESCRIPTION 2.1 Application 2.1.1 The MESA® SOLE is part of the MESA® line of Modular Electronic Sealed Architecture cabinets. The MESA® SOLE cabinet provides a flexible, economical housing within the network infrastructure. The cabinet is deployed in limited size and remote outside plant applications. 2.1.2 The cabinets offer a compact solution for housing electronics, protection, distribution, and battery backup.
Emerson Network Power Wireline Products 631-205-105 Version C, August 2009 2.2 Physical Specifications The MESA® SOLE is a welded 1/8-in. and .090 thick aluminum structure protected with an off-white multistage dry powder polyester paint finish for maximum durability and performance. The cabinet has two lifting eyes at the top that allow the enclosure to be lifted into mounting position using lifting equipment.
631-205-105 Version C, August 2009 Emerson Network Power Wireline Products 2.4 Cabinet Dimensions Height: • • • Without battery base: 33.02" (83.87 cm) Battery base for 60 Amp hr. batteries: 14.98" (38.05 cm) Total height with battery base installed: 48.00" (121.92 cm) Depth: 26.53" (67.39 cm) Width: 33.13" (84.14 cm without Customer Access Module) 43.13" (109.80 cm with Customer Access Module) Weight of Cabinet with Customer Access Module and Battery Base: • Empty cabinet approximately 309 lbs. (140.
Emerson Network Power Wireline Products 631-205-105 Version C, August 2009 2.5 Cabinet Features 2.5.1 Cabinet Access - The MESA® SOLE has an environmentally sealed door to access the equipment chamber. The cabinet has two 1/4-turn fasteners securing the door. The 1/4-turn fasteners are opened with a T-Handle tamper-resistant wrench, 5/16-inch hex/pin tool supplied with the cabinet. • For additional security, a padlock can be installed on the lower 1/4-turn security bolt.
631-205-105 Version C, August 2009 Emerson Network Power Wireline Products 2.5.11 Optional Customer Access Module - The MESA® SOLE cabinet can be ordered with an optional access module mounted on the right side of the cabinet. This module houses a 10-position ground bar and has mounting positions for customer equipment. This module is sealed from the outside environment by a right-hand hinged door, which is held in place by two 1/4-turn fasteners. The 1/4-turn fasteners are opened using a 216 hex tool.
Emerson Network Power Wireline Products 631-205-105 Version C, August 2009 3. OPENING AND CLOSING DOORS 3.0.1 Purpose - This section describes the locking mechanisms on the doors of the cabinet and explains how to open and close the doors. Refer to this section whenever instructed to open or close cabinet doors. 3.0.2 Lock Type - The MESA® SOLE cabinet has two 1/4-turn fasteners securing the door.
631-205-105 Version C, August 2009 Emerson Network Power Wireline Products 4. INSTALLATION CONSIDERATIONS 4.0.1 The MESA® SOLE cabinet can be wall, pole, or pad mounted. 4.1 Site Selection 4.1.1 Consider the following when deciding on the location for the MESA® SOLE cabinet: • • • • • • Before construction begins, obtain the rights-of-way from landowners, and other permits or approvals from public authorities.
Emerson Network Power Wireline Products 631-205-105 Version C, August 2009 ALERT TO AVOID EQUIPMENT DAMAGE: * DO NOT REMOVE - pallet and plastic covering from the cabinet until the cabinet is transported to the installation site. * Always ship and store the MESA® SOLE cabinet(s) on the pallet in an upright position to avoid possible damage to the internal equipment.
631-205-105 Version C, August 2009 Emerson Network Power Wireline Products Step 6: Place the gasket into position on the foundation pad so that the gasket will lie underneath the bottom of the cabinet when it is placed. The gasket should lie so the cutouts are in position around the conduit openings, and over the anchor bolts. Step 7: The front chamber door must stay open and the wind latch secured. OSP CABLE ENTRY Fig.
Emerson Network Power Wireline Products 631-205-105 Version C, August 2009 • Only specially trained operators shall be permitted to operate crane equipment for lifting and setting the cabinet. • Operators should not suspend loads over people, nor should any person work, stand, or pass under a suspended load. • Before lifting the cabinet, block off the area. Vehicles should not park within 25 feet (7.6 m) of the lifting circumference.
631-205-105 Version C, August 2009 Emerson Network Power Wireline Products Step 1: Insert the lifting cable sling connecting links securely through each of the two lifting ears (Fig. 7). To prevent the cabinet from tipping when the pallet brackets are removed, take up the slack with the crane. DO NOT tighten the cables so that the pallet lifts. The weight of the pallet will make it difficult to remove the bracket bolt. TWO SLINGS SHOULD BE USED - ONE FOR EACH EYEBOLT.
Emerson Network Power Wireline Products 631-205-105 Version C, August 2009 Step 3: Remove the bolts from the pallet mounting bracket, which secures the cabinet to the pallet.
631-205-105 Version C, August 2009 Emerson Network Power Wireline Products 5. PAD MOUNTING 5.0.1 Perform the following procedure to pad mount the MESA® SOLE cabinet. Step 1: Refer to Section 5.1 , "Concrete Foundation Pad Construction," Page 14 for recommended concrete pad construction. Step 2: Clean all litter from the foundation pad surface. Step 3: Dress the cable/conduit so that it will easily enter the cabinet splice chamber as it is being lowered onto the foundation pad.
Emerson Network Power Wireline Products 631-205-105 Version C, August 2009 5.1.2 Use concrete only for the foundation pad. Do not use substitute materials, such as reinforced plastics, since they lack the rigidity required for cabinet placement. Fig. 9 : Concrete Pad Template Diagram 5.1.3 The recommended concrete pad size is two feet (60.96 cm) beyond the perimeter of the cabinet, including the radius of any open doors. • Concrete pad dimensions: 48.00" x 35.31" (121.92 cm x 89.69 cm) 5.1.
631-205-105 Version C, August 2009 Emerson Network Power Wireline Products Square and level the template(s) on the stakes so the tops of the mounting plates are flush with, or no more than 0.25" (1/4-in). (6 mm) above, the top of the pad (Fig. 11). Square the template(s) so the diagonal measurement between the anchor bolts is equal. 48.00” REF 24.00" 18.00" 35.31" REF 28.00" 6.00” 6.00” .80” 1.25” 7.70” 3.50” 3.50” 3.50” 2.50” Fig.
Emerson Network Power Wireline Products 631-205-105 Version C, August 2009 CABLE CONDUITS 2" (5.08 cm) ABOVE CONCRETE PAD WOODEN FORM (2 x 6) TYPICAL 6" (15.24 cm) CONCRETE PAD " (5.08 cm) 16" STAKES SAND OR GRAVEL CABINET TEMPLATE FLUSH WITH, TO 1/4" (6.4 mm) ABOVE TOP OF CONCRETE 2" (5.08 cm) COMPACTED SOIL GROUND WIRE TO GROUNDING SYSTEM WELDED MESH 6 X 6 X 4/4 (4 GAUGE WIRE) Fig. 11 : Position of Conduit in Template (typical view) 6.
631-205-105 Version C, August 2009 Emerson Network Power Wireline Products 7. OPTIONAL BATTERY CHAMBER 7.0.1 The battery chamber is designed to hold one 60 amp-hour string of 12Vdc front-post batteries. Four batteries make one string. The batteries are installed in the chamber in one row of four batteries. Interior usable dimensions of the battery chamber are: Height: 13.00" (33.02 cm) Depth: 12.00" (30.48 cm) Width: 20.00" (50.8 cm) Fig.
Emerson Network Power Wireline Products 631-205-105 Version C, August 2009 8. HEAT EXCHANGER 8.0.1 The MESA® SOLE cabinet includes a door mounted heat exchanger which is capable of removing 650 Watts of heat at 65o. Fig. 13 : Door Mounted Heat Exchanger 8.1 Heat Exchanger Fans 8.1.1 The heat exchanger is a dual air chamber, vertical air flow device that keeps the temperature within the equipment manufacturer’s recommendations.
631-205-105 Version C, August 2009 Emerson Network Power Wireline Products 8.2.2 Refer to the documentation supplied with the cabinet for installation and operational instructions for the ECC. Fig.
Emerson Network Power Wireline Products 631-205-105 Version C, August 2009 9. MAINTENANCE 9.1 Optional Battery Chamber Filter Screen Maintenance Components: — Filter screen (F1002729) Step 1: Remove the #10 nuts securing the filter screen to the access panel (Fig. 15). Remove the filter screen. Set the nuts and access panel safely aside for later replacement. Fig. 15 : Filter Screen and Mounting Hardware Step 2: If compressed air is available, use it to blow off dust and dirt from the filter screen.
631-205-105 Version C, August 2009 Emerson Network Power Wireline Products 10. ACCESSORIES AND REPLACEMENT PARTS 10.0.1 Refer to Table A for a list of available features, accessories, and replacement parts. 10.0.2 Contact customer service at 800-800-1280 for information regarding replacement parts and/or accessories. TABLE A - Accessories and Replacement Parts Type Part No.
631-205-105 Version C, August 2009 Emerson Network Power Wireline Products NOTES: Emerson Network Power / 4350 Weaver Parkway / Warrenville, Illinois 60555 / (630) 579-5000 / FAX (630) 579-5050 © 2009 Emerson Network Power, Energy Systems, North America, Inc. All rights reserved. Any unauthorized reproduction or transmission without the prior consent of Emerson Network Power is prohibited. www.gotoemerson.com Specifications subject to change without notice.