User manual
Operation 41
Emerson Energy Systems
MFA150 Power System
NT6C28C User Manual
The mid trip circuit breaker will trigger an alarm only when it is
electrically tripped ( for example : overload ), not when it is manually put
in the OFF position.
Note : Circuit breakers with a capacity of more than 80 A must
be located adjacent to circuit breakers having a capacity
of less than 65 A.
Internal connecting features of the NT6C14GA/GM and NT6C14GP
control and distribution panels
The inside of the NT6C14GA/GB/GM and NT6C14GE/GF/GP control
and distribution panels contain the following terminal blocks and
connectors.
Terminal blocks
There is one 4-position screw-type terminal block (TB1) on the back of the
front door of the control and distribution panel to connect small loads to
QFF type fuses F1 to F4.
There are three 8-position screw type terminal blocks (TB1, TB2 and TB3)
on the controller card itself to interface with alarm signals, sensing signals
from busbars, FA IN signals from distribution fuses and circuit breakers,
and the battery disconnect panel, if provided.
Table 23 – TB1 and TB2 pin assignment on the controller card
TB1 pin No. Description TB2 pin No. Description
1 LVD ALARM (NC) 1 RFA (C)
2 LVD ALARM (C) 2 RFA MINOR (NC)
3 LVD ALARM (NO) 3 RFA MINOR (NO)
4 LVA (NC) 4 RFA MAJOR (NC)
5 LVA (C) 5 RFA MAJOR (NO)
6 LVA (NO) 6 FUSE ALARM
(NC)
7 EQL STAT (C) 7 FUSE ALARM (C)
8 EQL STAT (NO) 8 FUSE ALARM
(NO)