User manual
49
Emerson Energy Systems
MFA150 Power System
NT6C28C User Manual
Maintenance
Routine maintenance
The following is a list of general preventive maintenance procedures
which should be performed periodically as required by the environmental
conditions and the local maintenance policy to ensure trouble-free
operation of NT6C28C(x) MFA150 power system:
•
clean all ventilation openings
•
clean, or replace the filters ( if provided )
•
tighten all the electrical connections
•
check for hot fuses or breakers ( loose, undersized, or overloaded )
•
verify the alarm thresholds
•
verify the meter calibration
•
verify the rectifier settings
The detailed recommended maintenance and adjustment procedures for the
rectifiers and other components of the NT6C28C(x) MFA150 are covered
in their respective user manual ( refer to list in Appendix D ).
The following tools and test equipment are required to adjust equipment in
the power system. Also, have available User Manual Voltage_level
entitled Voltage Level Limits for Power Plants, Rectifiers and
Controllers :
•
potentiometer screwdriver, Bourns No. 60 or equivalent
•
digital voltmeter, Fluke 8050A or equivalent
•
dummy load, 100 A (or use the office load if available)