User manual
Maintenance 51
Emerson Energy Systems
MFA150 Power System
NT6C28C User Manual
Table 30 – Fault diagnosis ( continued )
Fault symptom Possible causes
Failure to generate an
RFA alarm under
appropriate conditions
Faulty rectifier
Faulty wiring
Faulty RFA MIN or RFA MAJ LED
Rectifiers are not sharing
the load
Incorrect float or equalize adjustment on one or
more of the rectifiers
Sense leads are open on one or more rectifiers
Share mode incorrectly set on one or more
rectifiers
LVD contactor does not
reconnect the load
Incorrect LVR or LVDR threshold setting
Faulty controller card or RPM1000C
Blown F1 fuse on the controller
(NT6C14GA/GB/GM and NT6C14GE/GF/GP)
or
LVD (NT6C14GC/GD/GN and
NT6C14GG/GH/GQ) card
Faulty contactor
On NT6C14GA/GM and NT6C14GP control and distribution panels only:
LV ALM lamp is lit
Low discharge voltage condition
Incorrect LV level adjustment
TST BYPASS lamp is lit The NORMAL/BYPASS switch is in the BYPASS
position on the controller card.
On NT6C14GC/GN control and distribution panels only:
UNIT lamp is lit red Failure of the RPM1000C
UNIT lamp is flashing Low voltage on the memory back-up battery of the
RPM1000C
AC lamp is lit AC supply for the rectifiers has failed.
FLOAT lamp is lit yellow
Slightly high or low discharge voltage condition
Incorrect HF or LF level adjustment
Incorrect float or equalize level adjustment on
one or more rectifiers
FLOAT lamp is lit red
High or low discharge voltage condition
Incorrect HV or LV level adjustment
Incorrect float or equalize level adjustment on
one or more rectifiers
BOD lamp is lit
Low discharge voltage condition
Incorrect BOD level adjustment
Incorrect float or equalize level adjustment on
one or more rectifiers
HVSD lamp is lit
A high voltage shutdown signal was sent to the
rectifiers by the RPM1000C
Incorrect HVSD level adjustment
FAN lamp lit Fan failure on one or more rectifiers
AUX lamp lit Auxiliary equipment failure (when programmed)
continued