Maintenance 53
Emerson Energy Systems
MFA150 Power System
NT6C28C User Manual
CAUTION
Precautions to take to avoid service interruptions
When working on a live power system, the low voltage
disconnect contactor (if provided) should be kept from
tripping. To do this, insert a 1/4-inch ( 3 mm ) wide
electrically isolated tool ( preferably plastic ) in the small
opening on the side of the contactor assembly to lock it
closed. See Figure 19.
Procedure 1 – Replacing the NT6C14PF controller card
Step Action
1
Notify the alarm centre of the possibility of incoming alarms during
the execution of this procedure.
2
If possible, use the TEST mode to record the existing alarm settings
of the control card.
3
Remove the top cover and open the front door of the control and
distribution panel.
4
If the system is provided with an LVD feature, insert a 1/4-inch ( 3
mm ) wide electrically isolated tool in the small side opening of the
contactor assembly to lock it closed as shown in Figure 19.
5
Remove the sense fuse on the front door of the control and
distribution panel and open the connector going to the controller
card.
6
Disconnect and insulate the red lead coming from TB3-4 on the
battery (–) charge busbar.
7
Remove and tag the power leads on TB3-3 and TB3-4 of the
controller card, as well as all the other alarm and control leads on
terminal block TB1, TB2 and TB3.
8
Unplug the rectifier and power plant alarm cable assemblies from
connectors J1 to J7.
9
Remove the mounting screw securing the controller card in place,
then pull the card slightly forward, slightly to the right, and pull it
forward completely to remove it.
10
Install the new card by reversing the operation in step 10 and
securing it in place with the mounting screw.
11
Reconnect all wires and cables by reversing steps 6, 7 and 8.
12 Adjustments
Put the BYPASS/NORMAL switch in the BYPASS position. The TST
BYPASS indicator should light up.
13
Connect an external digital multimeter set for a 60 V dc reading
across the test points located on the front of the control and
distribution panel.
continued